Bus Power
NetMeter continuously monitors the DeviceNet bus
power quality.
Display
What it means
Current network bus
voltage is 17.2V.
Minimum bus
voltage recorded
since NetMeter was
plugged in or reset is
17.1V.
Maximum peak-to-
peak (P-P) voltage
recorded since
NetMeter was
plugged in or reset is
0.6V.
Current peak-to-
peak (P-P) voltage
(transient or ripple)
is 0.1Vp-p.
Maximum bus
voltage recorded
since NetMeter was
plugged in or reset is
17.4V.
x1
x4
x3
x2
V
250
V
250
MIN
V
250
MAX
V
250
P-P
V
250
MAX
P-P
What’s a transient?
A transient is a short, temporary deviation of the bus
voltage level.
4
Every DeviceNet network has some level of bus power
transients, which is perfectly acceptable. Transients in
excess of 2V P-P can contribute to node failures and
communication errors in some cases and should be
investigated. Transients in excess of 10V P-P are an
indication of serious network problems..
10