[ENG] NetPing 2 IP PDU ETH 53R14 & NetPing 2 IP PDU GSM3G 203R15, User guide -[ENG][2PWR] Features of Local Controls,
LEDs, and Sockets on a Case of the Device
[ENG][2PWR] Features of Local Controls, LEDs, and Sockets on a Case of the Device
–
•
•
•
•
Element
Description
I1-I4
IO lines for connecting external sensors of "dry contact" and
controlling running devices.
Specification of the line in the "input" mode:
the voltage of the logic «1»: > 8,2 V;
the voltage of the logic «0»: < 3,5 V.
Line specification in the "output" mode:
the voltage of the logic «1»:
push-pull 12V, up to 200mA
;
the voltage of the logic «0»: 0V,
до
200mA.
SC/SD
A bus for connecting the i2C sensors
+5B
Power voltage for external sensors or running devices. An
acceptable range is 5..5,3V and output current is 250mA
G
Common