[ENG] 12.8. [DKSF 48.5 IU] How Can I Control The Device using SMS Commands?
The device has an ability to be controlled remotely using SMS commands.
THE SYNTAX OF SMS COMMANDS
The common format of an SMS command text:
where:
fff —
a code of a command, for example, Р1+ (see below).
community_w —
a password which corresponds to SNMP community for recording. It is set on the "
SETUP
" page of the device web-interface. It is
possible to use Latin letters, numbers, the "_" symbol without quotation marks and spaces.
kkkkk —a
request identifier (arbitrary number from 3 to 9 digits). It is repeated in the response to set the correspondence between the request
and the response. An optional command element. If the identifier is not in the command, you can not see it in the response.
THE CODES OF COMMANDS
The command code is indicated together, without any spaces.
The codes
of the
commands
The description
Pn+
Switch on the relay n, where n is the relay number
Pn-
Switch off the relay n, where n is the relay number
P*+
Switch on all the relays
P*-
Switch off all the relays
PnR
Reboot relay n, where n is the relay number
Pn?
Request relay state n, where n is the relay number
P?
Request the state of all the relyas in a short form
S?
Request the state of groups of outlets and inputs
Sx=y
Set the primary input y for the outlet group x, where y is the number of power input: 1 or 2; x - group number of outlets: 1 (outlets
1 ... 4) or 2 (outlets 5 ... 8)
SxB+
Allow input reservation for outlet group x, where x is the number of outlet group: 1 (outlets 1 ... 4) or 2 (outlets 5 ... 8)
SxB-
Forbid input reservation for outlet group x, where x is the number of outlet group: 1 (outlets 1 ... 4) or 2 (outlets 5 ... 8)
SxR+
Allow automatic return to the primary input for outlet group x, where x is the number of outlet group: 1 (outlets 1 ... 4) or 2 (outlets
5 ... 8)
SxR-
Forbid automatic return to the primary input for outlet group x, where x is the number of outlet group: 1 (outlets 1 ... 4) or 2
(outlets 5 ... 8)
NETPING fff community_w kkkkkk
The text of the command is case insensitive, it is possible to use lowercase and uppercase letters. Command elements are separated
by spaces. The characters (symbols) ‘(apostrophe),“ (quotation mark), @ are not allowed. Switching on these characters may cause a
firmware failure. A command completion is confirmed by a response message (see below).
The polarity (direction) of the relay switching when performing a reset must correspond to that specified in the settings
of the "Watchdog2 module (reset mode). If the relay is already in a reset state, the reset command has no effect,
although a response notification of successful execution of “NP DONE PnR” will be recieved.