Ping Polling Pause After Reset
(1 3600)
, s
–
— a field for setting the time for which polling is suspended after turning on the power channel socket.
A pause is necessary for the device to reboot, initialize and restore the functioning of its network interfaces. Otherwise, an endless repetition of
the operation of the "Watchdog" module is possible.
: 15 s.
In Default
Limit Number of Reset Retries (0 Disable, 1 255)
–
—
is a field for setting the number of consequent unsuccessful resets, after which functioning of
the «load» is not restored and there is still no response to ping. This can happen at the stable failure of the «load» that is impossible to restore by
switching the power on and off. When the limit of repeats is reached, resets are stopped, but a periodic ping request continues. Resets are
unlocked when there is a response on ping. Resets are stopped and a regular operation order is restored after a response to ping and everything
is recorded in the log. Parameter value 0 disables the limit. In Default 0.
:
Reset Polarity —is a field that allows indicating what action is going to be done to reboot the connected loadat outcoming terminals: «Switch
Relay Off» or «Switch Relay On» In
: Switch Relay Off.
default
Reset Condition Logic — determines a condition at which a device connected to terminals is going to be rebooted.
No reply from any of Address A, B, C — a connected device will be rebooted if at least one of addresses did not respond.
No reply from all of Address A, B, C — a connected device will be rebooted only if all requested addresses did not respond.
No reply from Address A and from one of B, C — a connected device will be rebooted if address А and any of addresses В or С, or both B and
C did not respond.
No reply from Address A, but B or C replies — connected device will be rebooted only if address A did not respond but address B and/or address
C responded. So, if all addresses do not respond, a connected device will not be rebooted.
After setting all necessary parameters, click the button «
», so that a device executes a command.
Apply changes
If one of the parameters is set incorrectly, it will be highlighted in red:
There is a need to correct a parameter value and click the button «
» one more time.
Apply changes
To understand the configuration process of the «
» module better, it is possible to read the article here
Watchdog
http://www.netpingdevice.com/bl
og/avtomaticheskaya-perezagruzka-zavisayushhego-routera-podklyuchennogo-k-netping-2-pwr-220-v3-eth