[ENG] 9.1. [DKSF 48.5 IU] Configuration of the AC Inputs in the Device`s Web Interface
The Configuration of the AC inputs if carried out on the "
" page ofthe device`s web interface. Here you can specify the input from
AC OUTLETS
which the power supply channel groups will be powered, as well as set additional automation settings for AC inputs:
In the power input configuration area, you can configure the following parameters:
Memo — a field for viewing or changing a brief description of power input. The maximum size is 30 characters.
: empty line.
In default
State of AC Input — a display of the voltage available at the inputs of the device. Possible states: «
», «
».
Voltage Ok
No Voltage
Connected Output Outlets — a display of the outlet groups connected to each power input.
Primary AC Input — setting the primary input for each outlet group. Both groups of outlets can be powered from a single input.
input 1
In default:
is primary for outlets 1 ... 4, input 2 is primary for outlets 5 ... 8
Enable AC Backup — a checkbox that allows the transition of a group of outlets to a backup input in case of absence of voltage at the primary
input.
.
: the checkbox is not set, the transition to the backup input does not occur
In default
Auto Revert to Primary AC Input — a checkbox, when installed, a group of outlets will be forced to switch to the primary input after voltage
appears on it.
: the checkbox is not set, auto-return to the primary input does not occur.
In default
Delay of Auto Revert, s — the delay time before returning to the primary input. 0-10 000 s.
0.
In default:
AC Backup is Active — a display of the status of the input backup function for each outlet group. Possible states: “
”, “
”.
On
Off
Manual Revert to Primary AC Input — a button, when clicked, the outlet group will switch from backup to primary input. when clicked, the outlet
group will switch from backup to main input. The button is active when the "
" mode is enabled for a group of outlets. This is an
Enable AC Backup
alternative to Auto Revert to Primary Input.
After changing all necessary parameters, press the "
" button.
Apply Changes
Switching of outlet groups between power inputs is accompanied by short-term shutdown of outlets!
When you switch off auto-revert to the primary input, after saving the relay settings, make sure that the group of outlets is connected to
the desired input, as it was intended. When the auto-revert is switched off, the device tends not to switch the input while saving the
settings, even if the primary input is changed in the new settings.