5
5. Data Report
Data report configuration and sending period are as following:
Example of ReportDataCmd
FPort
:
0x06
Bytes
1
1
1
Var
(Fix=8 Bytes)
Version
DeviceType
ReportType
NetvoxPayLoadData
Version
– 1 byte –0x01
——
the Version of NetvoxLoRaWAN Application Command Version
DeviceType
– 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType
– 1 byte –the presentation of the NetvoxPayLoadData
,
according the devicetype
NetvoxPayLoadData
– Fixed bytes (Fixed =8bytes)
Device
DeviceType
ReportType
NetvoxPayLoadData
R602A
0x69
0x01
Hearbeattime
(2Bytes,Unit:1s)
WarningStatus (1Byte)
0x00_NoWarnring,
0x01_Warning
Reserved
(5Bytes,fixed 0x00)
Uplink: 01 69 01 0E10 00 0000000000
heartbeat is 3600s and no
warning. //0E10 (H
ex)
= 3600
Min Interval (Unit: second)
Max Interval (Unit: second)
Any number between 1~65535
Any number between 1~65535
When the device is turned on, it will immediately send a version package.
Data will be reported by default setting before any configuration.
Default setting:
Maximum time: 3600s
Minimum time: 3600s (Mintime and Maxtime must be set to the same report time.
)
The reported data is decoded by the Netvox LoRaWAN Application Command document and
http://www.netvox.com.cn:8888/page/index