5
(2)
If R311FC had been joined into a LoRa network, remove and insert the batteries; the green
indicator will stay on for 5 seconds to show it joins into the network.
4.3 Function Key
(1)
Press and hold function key for 5 seconds to reset to factory setting. After restoring to
factory setting successfully, the green indicator will flashes quickly 20 times.
(2) Press function key; the green indicator will flash once and the device will send a data report.
4.4 Data Report
When the device is turned on, it will immediately send a version package.
Data will be reported once per hour by default setting.
Maximum time: 3600s
Minimum time: 3600s (Detect the current voltage value every 3600s by default setting)
Default reportchange:
Battery ---- 0x01 (0.1V)
Remarks:
1. The device periodically sends data according to the maximum time. The data content is:
R311FC current device status;
2. R311FC device will only report according to the minimum time when the battery voltage changes.
R311FC vibration alarm:
The device detects sudden movement or vibration, and the quiescent state changes. The device waits
for a certain period of time (DeactiveTime) to enter the quiescent state and calculate the duration,
sends a report of duration of vibrations, and restarts the calculation for the next detection. If the
vibration continues to occur within (DeactiveTime), the duration will be continuously calculated till
it enters the quiescent state.
Can sens downlink command through the gateway to change the device type, active vibration
threshold and DeactiveTime.
The Active vibration threshold range is 0x0003-0x00FF (default is 0x0003);
DeactiveTime is 0x01-0xFF (default is 0x05);
R311F
DeviceType(1Bytes,0x01_
R311FA
,0x02_
R311FC
,0x03_
R311FC
), the default value is the
programming value.
Data report configuration and sending period are as following: