Example of ConfigureCmd 

FPort

0x07 

 

Bytes 

Var (Fix =9 Bytes) 

 

CmdID 

DeviceType 

NetvoxPayLoadData 

CmdID

– 1 byte 

DeviceType

– 1 byte – Device Type of Device 

NetvoxPayLoadData

– var bytes (Max=9bytes) 

 

Description 

Device 

Cmd 

ID 

Device 

Type 

NetvoxPayLoadData

 

Config 

ReportReq 

R313CC 

0x01 

0x6C 

MinTime 

(2bytes 

Unit: s) 

MaxTime 

(2bytes 

Unit: s) 

Battery 

Change 

(1byte Unit: 0.1v) 

Reserved 

(4Bytes, Fixed 

0x00) 

Config 

ReportRsp 

0x81 

Status 

(0x00_success) 

Reserved 

(8Bytes, Fixed 0x00) 

ReadConfig 

ReportReq 

0x02 

Reserved 

(9Bytes, Fixed 0x00) 

ReadConfig 

ReportRsp 

0x82 

MinTime 

(2bytes 

Unit: s) 

MaxTime 

(2bytes 

Unit: s) 

Battery 

Change 

(1byte Unit: 0.1v) 

Reserved 

(4Bytes, Fixed 

0x00) 

 

(1)

 

Command Configuration:

 

    MinTime = 1min

MaxTime = 1min

BatteryChange = 0.1v 

     Downlink

  016C003C003C0100000000      003C(H

ex) 

= 60(D

ec) 

   

     Response

 

                816C000000000000000000 (Configuration success) 

                816C010000000000000000 (Configuration failure) 

(2)

 

Read Configuration:

 

     Downlink

  026C000000000000000000 

     Response

  826C003C003C0100000000

Current configuration

 

Summary of Contents for R313CC

Page 1: ...ogy Co Ltd This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of NETVOX Technology The specifications are subject to change without prior notice ...

Page 2: ...1 Table of Content 1 Introduction 2 2 Appearance 3 3 Main Features 3 4 Set up Instruction 4 5 Data Report 5 6 Installation 9 7 Important Maintenance Instruction 10 ...

Page 3: ... other communication methods LoRa spread spectrum modulation technique greatly extend the communication distance It can be widely used in any use case that requires long distance and low data wireless communications For example automatic meter reading building automation equipment wireless security systems industrial monitoring It has features like small size low power consumption long transmissio...

Page 4: ... data can be read and alerts can be set via SMS text and email optional Applicable to third party platforms Actility ThingPark TTN MyDevices Cayenne Low power consumption and long battery life Note Battery life is determined by the sensor reporting frequency and other variables please refer to http www netvox com tw electric electric_calc html On this website users can find battery lifetime for va...

Page 5: ...nductance and other energy storage components 3 Press any function key and insert batteries at the same time it will enter engineer testing mode Network Joining Never joined the network Turn on the device to search the network The green indicator stays on for 5 seconds success The green indicator remains off fail Had joined the network Turn on the device to search the previous network The green in...

Page 6: ...by the Netvox LoRaWAN Application Command document and http loraresolver netvoxcloud com 8888 page index Sleeping Mode The device is on and in the network Sleeping period Min Interval When the reportchange exceeds setting value or the state changes send a data report according to Min Interval Low Voltage Warning Low Voltage 2 4V 5 Data Report Data report configuration and sending period are as fol...

Page 7: ... 0x00 Config ReportRsp 0x81 Status 0x00_success Reserved 8Bytes Fixed 0x00 ReadConfig ReportReq 0x02 Reserved 9Bytes Fixed 0x00 ReadConfig ReportRsp 0x82 MinTime 2bytes Unit s MaxTime 2bytes Unit s Battery Change 1byte Unit 0 1v Reserved 4Bytes Fixed 0x00 1 Command Configuration MinTime 1min MaxTime 1min BatteryChange 0 1v Downlink 016C003C003C0100000000 003C Hex 60 Dec Response 816C00000000000000...

Page 8: ... based on MinTime 15 Minutes MaxTime 1 Hour Reportable Change i e BatteryVoltageChange 0 1V MaxTime Sleeping MinTime sleeping sleeping sleeping 0H 15th M 30th M 45th M 1H 2H Wakes up and collects data 2 8V Does not report Wakes up and collects data 2 8V Does not report Wakes up and collects data REPORT 2 8V Wake up and collects data REPORTS 2 8V Wakes up and collects data REPORTS 2 8V Wakes up and...

Page 9: ...e reports according to MaxTime interval 3 We do not recommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter resulting from data variation button pushed or MaxTime interval another cycle of MinTime MaxTime calculation is started Wakes up and collects data...

Page 10: ...reed switch and the magnet to the door or window in parallel as the figure on the right Note The installation distance between the reed switch and the magnet should be less than 2cm 3 When the door or window is opened the reed switch is separated from the magnet and the device reports the data immediately 4 If it detects that the battery voltage exceeds the variation during Min Time the data will ...

Page 11: ...melt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicate structures Do not clean the device with strong chemicals detergents or strong detergents Do no...

Reviews: