background image

 

5. Data Report   

 

 

 

 

 

 

 

 

The device will immediately send a version packet report along with two uplink packets including temperature, battery voltage, 

acceleration and velocity of the X, Y, and Z axes. 

The device sends data in the default configuration before any configuration is done. 

 

Default setting: 

MaxTime: Max Interval = 60 min = 3600s 

MinTime: Max Interval = 60 min = 3600s 

BatteryChange = 0x01 (0.1v) 

AccelerationChange = 0x0003 (m/s

2

)

 

ActiveThreshold = 0x0003   

InActiveThreshold = 0x0002 

RestoreReportSet = 0x00 (DO NOT report when sensor restore) 

Three-axis acceleration and velocity: 

If the three-axis acceleration of the device exceeds ActiveThreshold, a report will be sent immediately. After the 

three-axis acceleration and speed are reported, the three-axis acceleration of the device needs to be lower than 

InActiveThreshold, the duration is greater than 5s (cannot be modified), and the vibration stops completely, the next 

detection will start. If the vibration continues during this process after the report is sent, the timing will restart. 

The device sends two packets of data. One is the acceleration of the three axes, and the other is the speed of the three axes 

and temperature. The interval between the two packets is 15s. 

Note:   

(1)

 

The device report interval will be programmed based on the default firmware which may vary. 

(2)

 

The interval between two reports must be the minimum time. 

Please refer Netvox 

LoRaWAN Application Command document

 and 

Netvox Lora Command Resolver

 

http://loraresolver.netvoxcloud.com:8888/page/index

 to resolve uplink data. 

Summary of Contents for R718EC

Page 1: ...oprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written p...

Page 2: ...hold and InActiveThreshold 7 5 2 Calibration 7 5 3 Example of data configuration 7 5 4 Example for MinTime MaxTime logic 9 6 Example Application 10 7 Information about Battery Passivation 11 7 1 To de...

Page 3: ...onsumption Compared with other communication methods the LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low data wireless co...

Page 4: ...ping spread spectrum technology Configuration parameters can be configured through third party software platforms data can be read and alarms can be set via SMS text and email optional Available third...

Page 5: ...the device will be in engineering test mode Network Joining Never joined the network Turn on the device to search the network The green indicator stays on for 5 seconds success The green indicator re...

Page 6: ...After the three axis acceleration and speed are reported the three axis acceleration of the device needs to be lower than InActiveThreshold the duration is greater than 5s cannot be modified and the v...

Page 7: ...nActive Threshold 5 2 Calibration The accelerometer is a mechanical structure that contains components that can move freely These moving parts are very sensitive to mechanical stress far beyond solid...

Page 8: ...0x00 1 Configure device parameters MinTime 1min MaxTime 1min BatteryChange 0 1v Acceleratedvelocitychange 1m s2 Downlink 011C003C003C0100010000 003C Hex 60 Dec Device returns 811C000000000000000000 co...

Page 9: ...25th M 1H 40th M 1H 55th M 2H 10th M Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 6V Does not report Wakes up and collec...

Page 10: ...tus After installing and fixing R718EC please turn on the device After the device is joined one minute later R718EC would perform the calibration of the device the device cannot be moved after the cal...

Page 11: ...passivation may also lead to voltage delay when the batteries are put into operation and our devices may not work correctly in this situation As a result please make sure to source batteries from reli...

Page 12: ...lt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw...