background image

5

4. Set up Instruction

On/Off

Power on

Insert batteries. (The users may need a screwdriver to open.)

Turn on

Press and hold the function key for 3 seconds till the green indicator flashes once.

Turn off

(Restore to factory setting)

Press and hold the function key for 5 second, and the green indicator flashes 20 times.

Power off

Remove Batteries.

Note:

1. Remove and insert the battery; the device is at off state by default.

2. On/off interval is suggested to be about 10 seconds to avoid the interference of capacitor

inductance and other energy storage components.

3. The first 5 seconds after power on, the device will be in engineering test mode.

Network Joining

Never joined the network

Turn on the device to search the network.

The green indicator stays on for 5 seconds: success

The green indicator remains off: fail

Had joined the network

Turn on the device to search the previous network.

The green indicator stays on for 5 seconds: success

The green indicator remains off: fail

Function Key

Press and hold for 5 seconds

Restore to factory setting / Turn off

The green indicator flashes 20 times: success

The green indicator remains off: fail

Press once

The device is in the network: green indicator flashes once and sends a report

The device is not in the network: green indicator remains off

Sleeping Mode

The device is on and in the

network

Sleeping period: Min Interval.

When the reportchange exceeds setting value or the state changes: send a data report according to

Min Interval.

Low Voltage Warning

Low Voltage

3.2V

Summary of Contents for R718TB

Page 1: ...hnical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of...

Page 2: ...5 1 Example of ReportDataCmd 7 5 2 Example of ConfigureCmd 7 5 3 Example of ButtonPressTime 8 5 4 Example for MinTime MaxTime logic 9 6 Information about Battery Passivation 11 6 1 To determine whethe...

Page 3: ...er communication methods LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low data wireless communications For example automat...

Page 4: ...nfigured through third party software platforms data can be read and alarms can be set via SMS text and email optional Available third party platform Actility ThingPark TTN MyDevices Cayenne Low power...

Page 5: ...Never joined the network Turn on the device to search the network The green indicator stays on for 5 seconds success The green indicator remains off fail Had joined the network Turn on the device to s...

Page 6: ...in the default configuration before any configuration is done Default setting MaxTime Max Interval 60 min 3600s MinTime Max Interval 60 min 3600s BatteryChange 0x01 Unit 0 1v Note 1 By default it wil...

Page 7: ...adData Fixed bytes Fixed 8bytes Example of Uplink 0131012401000000000000 1st byte 01 Version 2nd byte 31 DeviceType 0x31 R718T R718TB 3rd byte 01 ReportType 4th byte 24 Battery 3 6v 24 Hex 36 Dec 36 0...

Page 8: ...ime 1min MaxTime 1min BatteryChange 0 1vFPort7 Downlink 0131003C003C0100000000 003C Hex 60 Dec Device returns 8131000000000000000000 configuration successful 8131010000000000000000 configuration faile...

Page 9: ...ration successful 8101 configuration failed 4 Read device parameters Downlink 02 Device returns 820A current device parameters 5 4 Example for MinTime MaxTime logic Example 1 based on MinTime 1 Hour M...

Page 10: ...ecommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter...

Page 11: ...passivation may also lead to voltage delay when the batteries are put into operation and our devices may not work correctly in this situation As a result please make sure to source batteries from rel...

Page 12: ...elt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not thro...

Reviews: