background image

 

5. Data Report   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.1 Example of ReportDataCmd 

FPort

0x06 

Bytes 

Var(Fix=8 Bytes) 

 

Version 

DeviceType 

ReportType 

NetvoxPayLoadData 

Version

– 1 byte –0x01

——

the Version of NetvoxLoRaWAN Application Command Version 

DeviceType

– 1 byte – Device Type of Device 

 

 

 

 

   

The devicetype is listed in Netvox LoRaWAN Application Devicetype doc 

ReportType

 – 1 byte –the presentation of the NetvoxPayLoadData

according the devicetype 

NetvoxPayLoadData

– Fixed bytes (Fixed =8bytes) 

When the device is powered on, it will immediately send a version package Report and the report data with the device 

battery voltage, the differential pressure, and the temperature. 

The device sends data in the default configuration before any configuration is done. 

Default setting: 

MaxTime: Max Interval = 15 min = 900s 

MinTime: Max Interval = 15 min = 900s 

BatteryChange = 0x01 (Unit: 0.1v) 

Different Pressure Change = 0x0A (1 Pa)  (Unit: 0.1Pa) 

Temperature Change = 0x0A (1°C)  (Unit: 0.

1℃

 

Measurement Range: 

Different pressure Measuring Range: -500 to 500 Pa 

Temperature Measuring Range: -

20℃ 

to 

50℃

 

 

Pressure Difference And Temperature Detection: 

When the function key is pressed, the device immediately sends a report with the current voltage value, differential 

pressure value and temperature value. Or when the configure time is up, it will also detect and send the report with 

Battery, Different Pressure, and Temperature. 

 

Note: Please refer Netvox 

LoRaWAN Application Command document

 and 

Netvox Lora Command Resolver

   

http://loraresolver.netvoxcloud.com:8888/page/index

 to resolve uplink data. 

Summary of Contents for R718Y

Page 1: ... proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties in whole or in part without written permission of NETVOX Technology The specifications are subject to change without prior notice Wireless Differential Pressure and Temperature ...

Page 2: ... 5 5 Data Report 6 5 1 Example of ReportDataCmd 6 5 2 Example of ConfigureCmd 7 5 3 Example for MinTime MaxTime logic 8 6 Information about Battery Passivation 9 6 1 To determine whether a battery requires activation 9 6 2 How to activate the battery 9 7 Important Maintenance Instruction 10 ...

Page 3: ...hods LoRa spread spectrum modulation method greatly increases to expand the communication distance Widely used in long distance low data wireless communications For example automatic meter reading building automation equipment wireless security systems industrial monitoring Main features include small size low power consumption transmission distance anti interference ability and so on LoRaWAN LoRa...

Page 4: ...configured through third party software platforms data can be read and alarms can be set via SMS text and email optional Available third party platform Actility ThingPark TTN MyDevices Cayenne Low power consumption and long battery life Battery Life Please refer to web http www netvox com tw electric electric_calc html At this website users can find battery life time for variety models at differen...

Page 5: ... Never joined the network Turn on the device to search the network The green indicator stays on for 5 seconds success The green indicator remains off fail Had joined the network Turn on the device to search the previous network The green indicator stays on for 5 seconds success The green indicator remains off fail Function Key Press and hold for 5 seconds Restore to factory setting Turn off The gr...

Page 6: ... in the default configuration before any configuration is done Default setting MaxTime Max Interval 15 min 900s MinTime Max Interval 15 min 900s BatteryChange 0x01 Unit 0 1v Different Pressure Change 0x0A 1 Pa Unit 0 1Pa Temperature Change 0x0A 1 C Unit 0 1 Measurement Range Different pressure Measuring Range 500 to 500 Pa Temperature Measuring Range 20 to 50 Pressure Difference And Temperature De...

Page 7: ... byte Device Type of Device NetvoxPayLoadData var bytes Max 9bytes Description Device CmdID Device Type NetvoxPayLoadData Config ReportReq R718Y 0x01 0xAC MinTime 2bytes Unit s MaxTime 2bytes Unit s BatteryChange 1byte Unit 0 1v DifferentPressure Change 2bytes Unit 0 1Pa TemperatureChange 2byte Unit 0 1 C Config ReportRsp 0x81 Status 0x00_success Reserved 8Bytes Fixed 0x00 ReadConfig ReportReq 0x0...

Page 8: ...tageChange 0 1V MaxTime sleeping sleeping 0H 15th M 30th M 45th M 1H 1H 10th M 1H 25th M 1H 40th M 1H 55th M 2H 10th M Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 6V Does not report Wakes up and collects data 3 6V Does not report Wakes up and collects data REPORTS 3 6V Wakes up and collects data REPORT 3 6V Wakes up and collects data REPORTS 3 6V Wakes up and colle...

Page 9: ...ergy density However primary lithium batteries like Li SOCl2 batteries will form a passivation layer as a reaction between the lithium anode and thionyl chloride if they are in storage for a long time or if the storage temperature is too high This lithium chloride layer prevents rapid self discharge caused by continuous reaction between lithium and thionyl chloride but battery passivation may also...

Page 10: ...melt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not throw knock or shake the device Rough handling of equipment can destroy internal circuit boards and delicate structures Do not clean the device with strong chemicals detergents or strong detergents Do no...

Reviews: