6
Example of ConfigureCmd
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 bytes
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Description Device
Cmd
ID
Device
Type
NetvoxPayLoadData
Config
ReportReq
R720C
0x01
0x70
MinTime
(2bytes Unit: s)
MaxTime
(2bytes Unit: s)
Battery
Change
(1byte Unit:0.1v)
Temperature
Change
(2byte
Unit:0
.01℃)
AirPress
Change
(2byte
Unit:0.1hPa)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes, Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes, Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit: s)
MaxTime
(2bytes Unit: s)
BatteryChange
(1byte Unit:0.1v)
Temperature
Change
(2byte
Unit:0.01℃)
AirPress
Change
(2byte
Unit:0.1hPa)
(1)
Configure R720C device parameter MinTime = 1min
、
MaxTime = 1min
、
BatteryChange = 0.1v
、
TemperatureChange=1
℃
(
100*0.01℃
), AirPressChange=1hPa (10*0.1hPa)
Downlink: 0170003C003C010064000A
Device return:
Uplink: 8170000000000000000000 (configuration success)
Uplink: 8170010000000000000000 (configuration failure)
(2)
Read R720C device parameter
Downlink: 0270000000000000000000
Device return:
Uplink: 8270003C003C010064000A (device current parameter)