E-SDS-TAA
SMOKE DETECTION SENSOR
Installation Instruction
The E-SDS-TAA is a smoke detection sensor intended for connection to an NTI E-16D/5D/2D (ENVIROMUX) for use in detecting
smoke in a server cabinet environment. When properly connected, the E-SDS-TAA will provide signals to the ENVIROMUX that
with proper configuration will result in alert messages being sent to the administrator of the ENVIROMUX.
Features Include:
For warning of smoke.
Photoelectric smoke detector.
Built-in 135° F (57° C) thermal heat sensor.
Includes mounting hardware.
Connect to RJ45 or digital input sensor ports.
Supports CAT5/5e/6 UTP or STP cables.
Voltage Supply: 8-35VDC
Current Consumption: 200uA
Alarm Output: Relay (NO)
Screw terminal
o
To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-
terminated end to the sensor screw terminal.
Maximum cable length: 1,000 ft (305 m)
Powered by E-2D/5D/16D.
Regulatory approvals: UL
TAA compliant
Installation
1. Connect two 18-22 AWG wires (not supplied) from any set of “Digital In” terminals (see below and on next page) on the
ENVIROMUX.
2. Connect the other end of those two wires to the switch terminals “C” and “N/O” on the smoke detection sensor.
3. Connect two more 18-22 AWG wires between the “12V” and “ “ (ground) terminals on the ENVIROMUX and the “12VDC”
and “
—
“ terminals on the smoke detector. Leave the “24VDC” terminal
unused
.
4. Be sure to tighten terminal screws to secure each conductor to the terminal block.
5. Mount the E-SDS-TAA where smoke detection is desired.
NETWORK
TECHNOLOGIES
INCORPORATED
Tel:330-562-7070
Fax:330-562-1999
1275 Danner Dr
Aurora, OH 44202
www.networktechinc.com
NTI
R
Note: The E-SDS-TAA is NOT intended
to be used as a primary fire and smoke
detection device.