E-SDS-TAA 

SMOKE DETECTION SENSOR 

 

Installation Instruction 

 
 
 
 
 

The E-SDS-TAA is a smoke detection sensor intended for connection to an NTI E-16D/5D/2D   (ENVIROMUX) for use in detecting 
smoke in a server cabinet environment.    When properly connected, the E-SDS-TAA will provide signals to the ENVIROMUX that 
with proper configuration will result in alert messages being sent to the administrator of the ENVIROMUX.    

Features Include:  

 

For warning of smoke. 

 

Photoelectric smoke detector. 

 

Built-in 135° F (57° C) thermal heat sensor. 

 

Includes mounting hardware. 

 

Connect to RJ45 or digital input sensor ports. 

 

Supports CAT5/5e/6 UTP or STP cables. 

 

Voltage Supply: 8-35VDC 

 

Current Consumption: 200uA 

 

Alarm Output: Relay (NO) 

 

Screw terminal  

o

 

To connect to the RJ45 inputs use CAT5/5e/6 cable terminated at one end with RJ45 connector. Connect the un-
terminated end to the sensor screw terminal. 

 

Maximum cable length: 1,000 ft (305 m) 

 

Powered by E-2D/5D/16D. 

 

Regulatory approvals: UL 

 

TAA compliant 

 

Installation

 

1.  Connect two 18-22 AWG wires (not supplied) from any set of “Digital In” terminals (see below and on next page) on the 

ENVIROMUX. 

2.  Connect the other end of those two wires to the switch terminals “C” and “N/O” on the smoke detection sensor. 
3.  Connect two more 18-22 AWG wires between the “12V” and “      “ (ground) terminals on the ENVIROMUX and the “12VDC”  
        and “

“  terminals on the smoke detector.  Leave the “24VDC” terminal 

unused

.  

4.  Be sure to tighten terminal screws to secure each conductor to the terminal block.  
5.  Mount the E-SDS-TAA where smoke detection is desired. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

NETWORK
TECHNOLOGIES
INCORPORATED

Tel:330-562-7070
Fax:330-562-1999

1275 Danner Dr
Aurora, OH 44202

  www.networktechinc.com

NTI

R

Note: The E-SDS-TAA is NOT intended 
to be used as a primary fire and smoke 
detection device.  

Summary of Contents for E-SDS-TAA

Page 1: ...ated at one end with RJ45 connector Connect the un terminated end to the sensor screw terminal Maximum cable length 1 000 ft 305 m Powered by E 2D 5D 16D Regulatory approvals UL TAA compliant Installation 1 Connect two 18 22 AWG wires not supplied from any set of Digital In terminals see below and on next page on the ENVIROMUX 2 Connect the other end of those two wires to the switch terminals C an...

Page 2: ...n the smoke detection sensor Note DO NOT connect the 12VDC adapter to the terminal labeled 24VDC 2 Connect the wire labeled NEG to the terminal labeled negative on the smoke detection sensor Alternative Sensor Connection If a connection to an available RJ45 Sensor input is desired CAT5 5e 6 patch cable can be used by cutting off one end and terminating to the sensor as illustrated to the right ...

Page 3: ...n the E SDS TAA will close to generate an alert message from the ENVIROMUX For maintenance and testing instruction see the instructions that are included from the sensor manufacturer with this kit Example of sensor configuration in ENVIROMUX In the event the smoke detector should be placed in alarm condition it must be power cycled in order to reset it To quickly cycle the power when connected to ...

Page 4: ...ts reserved No part of this publication may be reproduced stored in a retrieval system or transmitted in any form or by any means electronic mechanical photocopying recording or otherwise without the prior written consent of Network Technologies Inc 1275 Danner Drive Aurora Ohio 44202 CHANGES The material in this guide is for information only and is subject to change without notice Network Technol...

Reviews: