OPERATING & ASSEMBLY INSTRUCTION

®

powerCON

   Locking 3 pole Power Connector

R

Page 1

BDA 452

A.

  OPERATING INSTRUCTION

IMPORTANT SAFETY INSTRUCTION:

The powerCON system is certified as connector without breaking capacity according IEC 61984 / VDE 0627. 
In this standard the term connector (without breaking capacity) refers to components which in normal use are not to 
be engaged or disengaged when under load or live.

Connector Combination & Keyways:

With the two non-interchangeable types of connectors (A type and B type) it is impossible to produce a short circuit. 
Mating connectors (combination) are identified by mechanical keyways and by color.

LIE

CH

TE

NS

TE

IN

LIE

CH

TE

NS

TE

IN

A type (color coding blue)
POWER IN

B type (color coding gray)
POWER OUT

B.

  ASSEMBLY INSTRUCTION

Place the bushing (1) and the chuck (2) over 
the cable.

  White chuck (a):

      6.0 - 11.0 mm

 [0.236 - 0.433”]

  Black chuck (b):

    9.5 - 15.0 mm

 [0.374 - 0.59”]

 

VDE:    9.5 - 14.0 mm

 [0.374 - 0.551”]

Prepare the cable as shown.

  Cable O.D.

:   6.0 - 15.0 mm

 [0.236 - 0.59”]

2

  Wire size

:     2.5 mm

 (AWG 14)

Insert the wire into the terminals and fasten 
the clamping device with a POZIDRIV® #1, 
max. Torque 0.5 Nm (0.37 lb-ft).

B

A

B

[0.32"]

8 mm

[0.787”]

20 mm

[0.9”]

PE 23 mm

NAC3MPA-1

NAC3FCA

NAC3MPB-1

NAC3FCB

C

Torque Value 0.5 Nm

POZIDRIV®  #1

N

L

WIRING

C

ð

or

1.

2.

b

a

A