New Air Refrigeration
INSTALLATION
& OPERATION
OPERATION
8
NIF-CG Series: Installation & Operation
1. Electical:
Please ensure that the required voltage of the compressor is maintained at all times. Low
or high voltage can affect the refrigeration unit. All units should be plugged into a grounded and
properly-sized electrical outlet, with appropriate overcurrent protection. Please refer to the electrical
requirements on the nameplate of the unit. Please make sure that your unit has its own dedicated
outlet. Do not use an extension cord.
• Specified capacity of the wire is 10A. Section squares of the wire is 0.82mm2. Single line or
compound lines are all allowed. The fuse of 2.5A specified electric current should be installed.
(Power cord should be replaced with the same of 6A and 0.82mm2, when it is damaged).
• Single-phase power supply, 60Hz, voltage 115V. If the voltage is unstable, please install a voltage
stabilizer with capacity above 1000W.
• Avoid turning on and off the power too frequently. If the power is turned off, wait 5 minutes
before turning it on again.
• When the freezer will be out of use for a long time, disconnect the power first, then clean it.
Please examine the circuit whether it is in excellent condition before reuse.
2. Loading Product:
There must be space between the foods stored in the cabinet, between the foods
and the inner surface of the cabinet, so as to keep good ventilation of cold air and freeze evenly. Do
not put in any bottled or canned beverage with freezing point above the temperature in the cabinet
when it is below zero.
• For foods that should be moisture-free (or lose water easily), wrap them up with hermetically
sealed food bags or fresh films before putting in the cabinet for the sake of avoiding smell-mixing
and reducing frosting.
• Storage of volatile and combustible gases, liquids such as strong alkalies, strong acids, gas, etc. is
forbidden.
PLEASE NOTE:
Excessive door openings should be avoided in order to maintain cabinet temperature
and to eliminate the possibility of coil freeze-up.