10
It is necessary to operate the detector during inspection or maintenance work. Therefore,
leave a distance of 50cm or more between the front side of the detector and the object in front
of it when installing it.
・
When installing this diffusion type gas detector on the ceiling or a higher location, make sure to
leave enough space just below the detector to allow for inspection or maintenance activities.
When installing the detector at a height more than 3m from the floor, we recommend you to
use a suction type gas detector with a sampling tube up to the ceiling.
A sensor guard is not necessary when installing the detector on the ceiling or a higher location.
However, when installing the detector on a lower place like the floor, a sensor guard is required
in order to protect the sensor from water splash.
Consider the direction of the gas flow and the hole of the sensor guard when installing.
Leave a distance of min. 50cm.
Gas flow
Install the sensor guard so that
the gas flows through the hole.
Leave space below the gas
detector for inspection or
maintenance purposes.