Dimension
Width × Height× Length
:
7.4 mm × 95.2 mm × 70 mm
Installation
The apparatus can be mounted on a 35 mm standard
rail corresponding to DIN EN 60715, they must be
snapped onto the rail, and never slanted or tipped to
the side.
Requirements for installation
In the safe zone, surge protective devices and safety
barrier can be installed in the same or different cabinet,
but can not be installed on the same track side by
side.
The cables (and wires) associated with the safety and
the hazardous area should be wired and laid
separately.
Installation steps are as follows:
Installation
Make the metal bayonet locked into the guide rail,
push the SPD in the rail as the direction of the arrow
in the above.
Removing steps are as follows:
Removing
First, pry the metal lock off the rail with screwdriver as
arrow shown, pull downward the springs, and rotate
the SPD, then remove it.
Connections
Using M3 screwdriver;
M3
Wire size is 0.2 mm
2
~
2.5 mm
2
;
2.5 mm
2
Maximum torque of the screw is 0.5 N.m;
Max. 0.5 N.m
Attentions
The current Input Isolated Safety Barriers was
constructed in protection degree IP 20 and must
therefore be protected from undesirable ambient
conditions (water, small foreign objects). It is suitable
for installed in control room or high density field
cabinet, convenient for installation and displacement.
The devices were designed for use in pollution degree
2 and overvoltage category III as IEC/EN 60664-1. If
used in areas with higher pollution degree, the devices
need to be protected accordingly.
Installation position shall not be affected by strong
mechanical vibration, impact and electromagnetic
induction from signal terminal and power supply,
should conformity with the requirements on
electromagnetic interference resistance of products in
Class 3 industrial field atmosphere stipulated in IEC
61000-4, and the atmosphere shall be free from
gases that are corrosive to metal and plastic
components.
Before installation, please check the surge protector is
intact or not. If have any damage, it should not be
installed.
Only using the SPD according to this document, if
more than the rated value, SPD and other device are
likely to be damaged.
Devices must only be repaired directly by the
manufacturer. Tampering with the apparatus is
dangerous and therefore forbidden.
Supplements
The apparatus must be installed, connected and
adjusted by qualified personnel in non-hazardous area
according with the instruction manual.
If faults cannot be eliminated, the apparatus must be
taken out of operation and protected from being
placed in service again inadvertently. Devices must
only be repaired directly by the manufacturer.
Tampering with the apparatus is dangerous and
therefore forbidden.
The operator must strictly comply with the relevant
local safety standards and guidelines.
If there is any content difference between the
specification and the website or sample, the
instructions shall prevail. We reserve the rights to
change or update the product information without prior
noticing the users.