29
110839-01 -8/20
AP-U
Installation & Service Manual
WARNING: DO NOT ADD WATER UNTIL THE
BOILER HAS FULLY COOLED.
To activate Manual Reset LWCO mode
1. Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro
2. Turn the HI TEMP dial to select feature 3
3. Push the Test/Setting Button to A for
Automatic Reset Mode
4. Reset LO TEMP and HI TEMP settings to
desired temperatures.
To Test the Manual Reset Feature:
Press and hold the
Test/Settings button located on the top of the control
for 30 seconds to simulate a low water condition. After
30 seconds, the Low Water light will blink indicating
that the control is locked out. To reset the lock-out
condition, press the Test/Setting button momentarily.
4.
Circulator Activation Options
When in the default mode, the HydroStat
activates the circulator (
C1/C2
contacts) on
calls to
TT
.
The control can be programmed
to activate the circulator on calls to
ZC/ZR
in
place of, or in addition to
TT
.
To change how the Circulator is activated
1. Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro
2. Turn the HI TEMP dial to select feature 4
3. Push the Test/Setting Button to select
between the following options:
A - Circulator on
TT
call only
b - Circulator on
ZC/ZR
calls
C - Circulator on both
TT
&
ZC/ZR
calls
4. Reset LO TEMP and HI TEMP settings to
desired temperatures.
5.
Circulator Hold Off (Enhanced Condensing
Protection)
To reduce the potential for condensing, On
a call for heat the control will allow
the boiler to heat to 125oF prior to energizing
the circulator. Once energized, the circulator
will remain on for the duration of the heating
call unless the boiler temperature drops below
115oF. If this occurs, the circulator will
re-energize when the boiler returns to 125oF.
Circulator Hold Off will expire after 15
minutes.
To activate Circulator Hold Off
1. Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro
2. Turn the HI TEMP dial to select feature 5
3. Push the Test/Setting Button to Circulator
Hold Off ON or OFF
4. Reset LO TEMP and HI TEMP settings to
desired temperatures.
6.
Setting the Well Type (Elctro-Well vs.
Standard Immersion Well)
When used to replace older temperature-
only controls, the HyrdroStat can be installed
on the existing well. (The Hydrolevel Elctro-
Well is required to activate low water cut-off
operation. Older wells may contain hardened
heat transfer grease or other contaminants
that could interfere with metal-to-metal
continually between the sensor head and the
inside of the well. Insufficient contact could
lead to false low water conditions and burner
shut downs. Setting the well type to
Standard Well prevents the possibility of
this occurring.
To change the well type
1. Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro
2. Turn the HI TEMP dial to select feature 8
3. Push the Test/Setting Button to select A for
Electro-Well or b for Standard Well.
NOTE: To ensure that the low water cut-off is always
active when the control is installed on an Electro-
Well, setting b will ONLY be available when installed
on a standard well. The HydroStat sensor checks to
determine if a standard well is used by looking for low
resistance to ground, a condition that can only exist
with a standard well. If you are installing on a standard
well and either Low Water LED’s are on, setting b
will not be available. Check to see if the inside of
the well tube is badly oxidized or contaminated with
heat transfer grease. It may be necessary to clean
the well to allow for setting b to be selected (See
Troubleshooting Guide for more information).
7.
High Limit Differential
When the Economy feature is on, the
control’s Thermal Targeting feature
actively sets varying differentials based on
system conditions. This option allows for
selecting a 10, 20 or 30 degree fixed
differential when the Economy feature
is turned OFF. These optional differential
settings are subtractive from the HIGH LIMIT
setting.
Note:
If the Economy feature in on,
this setting will be overridden by the control’s
Thermal Targeting function.
To change the high limit differential
1. Turn the LO TEMP dial to access the
Program Mode - indicated in the display as
Pro
2. Turn the HI TEMP dial to select feature 9
3. Push the Test/Setting Button to select a
high limit differential of 10, 20, or 30
4. Reset LO TEMP and HI TEMP settings to
desired temperatures.
8
Operating
(continued)
Summary of Contents for AP-U AP-110U-N
Page 41: ...41 110839 01 8 20 AP U Installation Service Manual This page intentionally left blank...
Page 46: ...46 110839 01 8 20 AP U Installation Service Manual SERVICE RECORD SERVICE PERFORMED DATE...
Page 47: ...47 110839 01 8 20 AP U Installation Service Manual SERVICE RECORD SERVICE PERFORMED DATE...
Page 48: ...48 110839 01 8 20 AP U Installation Service Manual...