background image

24

X. Troubleshooting

A.

  BEFORE TROUBLESHOOTING

   The following pages contain troubleshooting tables for 

use in diagnosing control problems.  When using these 

tables the following should be kept in mind:
1.  This information is only meant to be used by 

a professional heating technician as an aid in 

diagnosing boiler problems.

2.  In general, these tables assume that there are no 

loose or miswired electrical connections.  Before 

using these tables inspect all electrical connections 

on the boiler to make sure that they are tight.  Also, 

check the wiring on the boiler against the wiring 

diagram in Figures 9 and 10.  Ensure that incoming 

120 Vac power polarity is correct and that the boiler 

is properly grounded. Further, ensure that the control 

power supply is 24 VAC (minimum 18 VAC to 

maximum 30 VAC) and polarity is correct.

4.  All controls on the CG-E Series are tested at least 

once in the manufacturing process and a defective 

control or component is generally the least likely 

cause.  Before replacing a component, try to rule out 

all other possible causes.

5.  When checking voltage across wiring harness pins 

be careful not to insert the meter probes into the 

pins.  Doing so may damage the pin, resulting in a 

loose connection when the harness is reconnected.

Table 3:  Troubleshooting Using the Control's LED

Flashing  LED

Fault Condition

POWER

     Steady 1 Hz flash

     Flash code 2

     Flash code 3

     Flash code 4

     Flash code 5

     Flash code 6

Reverse polarity of 115 VAC supply voltage

Faults internal to microprocessor (RAM, ROM, etc.)

Unused

Unused

Water thermistors disagree

Gas valve outputs in improper state

POWER + TSTAT/CIRC

48 volts on Thermostat circuit

DAMPER

Damper switch opened after it had  been proved closed.  Continues flashing until demand for heat 

removed or Damper switch proven closed in ignition sequence.

POWER + DAMPER

Damper switch stuck open or closed (control in damper switch lockout)

LIMIT

Fault detected in temperature sensing hardware

FLAME

Flame loss, or flame not sensed during trial for ignition.  Continues flashing until either flame is 

established or demand for heat is removed.

POWER + FLAME

Flame sensed without call for heat or out of sequence during ignition trial.

Lockouts

1.  Lockout from internal hardware faults (listed above under POWER) automatically resets after the hardware fault has 

not been present for 60 minutes.  Lockouts from internal hardware faults may not be manually reset except by removing 

power from the control.

2.  Lockout from damper switch failing to close within 45 seconds automatically resets after 60 minutes.  Lockout may be 

manually reset by opening the thermostat for more than 2 but less then 20 seconds.

Summary of Contents for CG-E SERIES

Page 1: ...eating Contractor Phone Number Address INSTALLATION OPERATING AND SERVICE INSTRUCTIONS CG E Series GAS BOILER BEFORE INSTALLATION READ THIS MANUAL SAVE THESE INSTRUCTIONS Installing contractor and hom...

Page 2: ...n or maintenance which are important but not related to personal injury hazards The City of New York requires a Licensed Master Plumber supervise the installation of this product The Massachusetts Boa...

Page 3: ...ments 120VAC 60 Hz 1 ph Less than 12A Maximum Allowable Working Pressure 50 psi Boiler shipped from factory with a 30 psi relief valve Boiler Model Input MBH 1 Shipping Weight lbs Empty Weight lbs Wat...

Page 4: ...4 Figure 1 Minimum Clearance to Combustible Materials and Alcove Dimensions...

Page 5: ...if floor is not level or if water may be encountered on floor around boiler CAUTION ASSURE THAT THE FRONT AIR DAM is in place and undamaged A damaged front air dam will negatively affect the performan...

Page 6: ...t be installed with chilled medium piped in parallel with the heating boiler using appropriate valves to prevent chilled medium from entering boiler See Figure 3 Also consult Residential Hydronic Heat...

Page 7: ...according to the LWCO manufacturer s instructions 2 The recommended location for a LWCO on gas hot water boilers is above the boiler in the supply piping The minimum safe water level of a water boile...

Page 8: ...8 Figure 5 Recommended Water Piping for Zone Valve Zoned Heating Systems...

Page 9: ...9 Figure 6 Recommended Water Piping for Circulator Zoned Heating Systems...

Page 10: ...tile lining will cause severe injury or death B Inspect chimney and remove any obstructions or restric tions Clean chimney if previously used for solid or liquid fuel burning appliances or fireplaces...

Page 11: ...e of a match or candle or smoke from a cigarette cigar or pipe f After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlin...

Page 12: ...pe resistant to action of liquefied petroleum gas V Gas Piping Figure 8 Pilot and Gas Piping 3 Install sediment trap ground joint union and manual shut off valve upstream of boiler gas control valve S...

Page 13: ...than 12 amperes A separate electrical circuit must be run from the main electrical service with an over current device disconnect in the circuit A service switch is recommended and may be required by...

Page 14: ...14 Figure 9 Wiring Connection Diagram...

Page 15: ...15 Figure 10 Schematic Ladder Diagram...

Page 16: ...16 Figure 11 Wiring Schematic Zone Valves Figure 12 Wiring Schematic Zone Circulators...

Page 17: ...main burners has been off for at least five minutes and vent damper has been in the open position 4 Turn OFF the electric switch serving boiler 5 Open valve on main gas line at meter 6 Purge air from...

Page 18: ...18 Figure 14 Operating Instructions...

Page 19: ...should not be confused with true yellow tipping E Check Pilot Burner Flame 1 See Figure 16 The pilot burner should be lit only if thermostat is calling for heat The pilot burner produces three 3 flam...

Page 20: ...at call for heat is wired to the DHW input the control starts the circulator and if the boiler temperature is less than the operating setpoint less differential the vent damper is energized without de...

Page 21: ...ial Setpoint when outdoor sensor installed The Outdoor Reset Differential Setpoint is user adjustable by turning the bottom knob labeled OUTDOOR RESET DIFF Adjustment range is 0 F to 50 F When no outd...

Page 22: ...respirator 2 Long sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clo...

Page 23: ...ire plug at the gas valve d Remove wires to flame roll out switch e Remove the burner access panel f Mark the location of the pilot main burner on the manifold if the marking on manifold is missing or...

Page 24: ...on when the harness is reconnected Table 3 Troubleshooting Using the Control s LED Flashing LED Fault Condition POWER Steady 1 Hz flash Flash code 2 Flash code 3 Flash code 4 Flash code 5 Flash code 6...

Page 25: ...adjust thermostat or remove wire from TT terminals Check for 24Vac between P6 5 and ground If voltage not present attempt to start boiler again If 24Vac is present unplug the vent damper harness from...

Page 26: ...by a collapsed chimney resulting in full or partial blockage chimney cross sectional area too small height insufficient or cold chimney causing sustained poor draft Always follow the recommendations...

Page 27: ...rculator is On But Damper is Not Open LED Status Recommended Corrective Action POWER TSTAT CIRC LIMIT Damper Failed to Open The control is waiting for the damper to open Damper end switch has failed t...

Page 28: ...as flow check the following 24 volts across PV and MV PV at gas valve if voltage ok replace defective gas valve Check for break in wiring harness to gas valve 24 volts across control connector P4 6 an...

Page 29: ...rea or have questions regarding the availability of New Yorker products or repair parts please contact New Yorker Boiler Company Inc P O Box 10 Hatfield Pennsylvania 19440 0010 Attn Customer Service D...

Page 30: ...y Complete 102287 03 1 102287 04 1 102287 05 1 102287 06 1 102287 07 1 102287 08 1 102287 09 1 1B Canopy Gasket Kit 6201001 1 1 1 1 1 1 1 1C Canopy Assembly 102254 03 1 102254 04 1 102254 05 1 102254...

Page 31: ...31 Section Assembly and Canopy Group...

Page 32: ...ssembly 61807031 1 61807041 1 61807051 1 61807061 1 61807071 1 61807081 1 61807091 1 2D Base Front Panel 102705 03 1 102705 04 1 102705 05 1 102705 06 1 102705 07 1 102705 08 1 102705 09 1 2E Burner A...

Page 33: ...7042 1 72007052 1 72007062 1 72007072 1 72007082 1 72007092 1 2K Base Leg Assembly 6186001 4 4 4 4 4 4 4 2L Flame Roll out Switch 80160044 1 1 1 1 1 1 1 2M Manifold Support Bracket 718070001 1 1 1 1 1...

Page 34: ...1 82207051 1 82207061 1 82207071 1 82207081 1 82207091 1 3C Main Burner Orifice 47 White Nat Gas 822710 4 6 8 10 12 14 16 3C Main Burner Orifice 1 20 mm LP 822792 4 6 8 10 12 14 16 3D Main Burner w 60...

Page 35: ...rol Atmospheric Draft UTEC 1135 630 106541 01 1 1 1 1 1 1 1 4B Transformer 40 VA modified Honeywell AT140B1297 106529 01 1 1 1 1 1 1 1 4C Limit Rated Temperature Sensor 12 Lg Tasseron 106643 01 1 1 1...

Page 36: ...6 Key No Description Part Number CG E MODEL 30 40 50 60 70 80 90 Jacket Assembly Complete 5 Jacket Assembly Complete 106707 03 1 106707 04 1 106707 05 1 106707 06 1 106707 07 1 106707 08 1 106707 09 1...

Page 37: ...1 1 1 1 1 1 1 6C Safety Relief Valve 30 psi 81660363 1 1 1 1 1 1 1 6D Drain Valve 102802 01 1 1 1 1 1 1 1 6E Vent Damper 4 Dia 102284 01 1 Vent Damper 5 Dia 102284 02 1 Vent Damper 6 Dia 102284 03 1 1...

Page 38: ...38...

Page 39: ...39...

Page 40: ...40...

Reviews: