background image

22

R.

  Boil-out boiler.

1.  Follow instructions TO TURN OFF GAS TO 

APPLIANCE.  See Figure 21 for continuous 

ignition (standing pilot) or Figure 22 for intermittent 

ignition (EI).

2.  Drain boiler until 1" of water is visible in gauge 

glass.

3.  Run temporary hose or piping from boiler drain 

valve to an open drain or some other location where 

hot water may be discharged safely.  Do not install 

valve in this line.

4.  Drain about 5 gallons of hot water from boiler into a 

container and dissolve into it an appropriate amount 

of recommended boil out compound.  Remove 

safety valve and add solution to boiler water through 

exposed tapping using a funnel.

E

C

I

T

O

N

l

a

c

o

l

t

l

u

s

n

o

c

r

o

s

e

i

t

i

r

o

h

t

u

a

l

a

c

o

l

h

t

i

w

k

c

e

h

C

e

l

b

a

t

p

e

c

c

a

r

o

f

s

e

c

i

v

r

e

s

t

n

e

m

t

a

e

r

t

r

e

t

a

w

.

s

d

n

u

o

p

m

o

c

g

n

i

n

a

e

l

c

l

a

c

i

m

e

h

c

5.  Run temporary hose or piping from boiler tapping 

"E" to an open drain or some other location where 

hot water may be discharged safely.  Do not install 

valve in this line (See Figure 4).

6.  Follow Lighting or Operating Instructions to place 

boiler in operation.  See Figure 21 for continuous 

ignition (standing pilot) or Figure 22 for intermittent 

ignition (EI).

7.  Operate sufficiently to boil the water without 

producing steam pressure.  Boil for about 5 hours.  

Open boiler fill valve sufficiently to permit a steady 

trickle of water from the pipe.  Continue this slow 

boiling and trickle of overflow for several hours 

until the water coming from the overflow is clear.

8.  Follow instructions TO TURN OFF GAS TO 

APPLIANCE.  See Figure 21 for continuous 

ignition (standing pilot) or Figure 22 for intermittent 

ignition (EI). 

9.  Drain boiler in a manner and to a location that hot 

water can be discharged with safety.

10. Refill boiler to normal water line.  If water in gauge  

 glass does not appear to be clear, repeat steps (1  

 thru 3) and boil out the boiler for a longer time.

S.

  Second Boilout for Stubborn Cases.

 If unsteady water 

line, foaming or priming persist, proceed as follows:
1.  Connect hoses from boiler and return main drain 

valves to floor drain.  Close shut off valve in 

Hartford Loop and open drain valve in return main.  

Fill boiler to normal water level.

2.  Follow Lighting or Operating Instructions to place 

boiler in operation.  See Figure 21 for continuous 

ignition (standing pilot) or Figure 22 for intermittent 

ignition (EI).

3.  Operate boiler at this water level for at least 30 

minutes after the condensate begins to run hot.

4.  Follow instructions TO TURN OFF GAS TO 

APPLIANCE.  See Figure 21 for continuous 

ignition (standing pilot) or Figure 22 for intermittent 

ignition (EI). 

5.  Close all radiator valves.  Remove all supply main 

air valves and plug the openings in supply main.

6.  Draw about 5 gallons of hot water from boiler into a 

container and dissolve into it the appropriate amount 

of a recommended boilout compound.  Remove 

safety valve from boiler and pour this solution into 

boiler, then reinstall safety valve.

7.  Follow Lighting or Operating Instructions to place 

boiler in operation.  See Figure 21 for continuous 

ignition (standing pilot) or Figure 22 for intermittent 

ignition (EI).

8.  Keep operating boiler while feeding water to boiler 

slowly.  This will raise water level in boiler slowly 

so that water will be boiling hot and will rise slowly 

into supply main and back through return main, 

flowing from drain hose at about 180°F.  Continue 

until water runs clear from drain hose for at least 30 

minutes.

9.  Stop feeding water to boiler but continue operating 

boiler until excess water in boiler flows out through 

supply main and water lowers (by steaming) until it 

reaches normal level in boiler. 

10. Follow instructions to TURN OFF GAS TO    

 APPLIANCE.  See Figure 21 for continuous   

 ignition (standing pilot) or Figure 22 for  

 

 intermittent ignition (EI).

11. Drain boiler.  Open all radiator valves.  Reinstall  

 all supply main air valves.  Open shut off valve in  

 Hartford Loop.

12. When boiler has cooled down sufficiently (iron  

 sections are not too hot to touch), close the drain  

 valves at boiler and in return main and feed water  

 slowly up to normal level in boiler.

13. Follow Lighting or Operating Instructions to place    

 boiler in operation.  See Figure 21 for continuous  

 ignition (standing pilot) or Figure 22 for  

 

 intermittent ignition (EI).

14. Allow boiler to steam for 10 minutes.
15. Follow instructions to TURN OFF GAS TO    

 APPLIANCE.  See Figure 21 for continuous   

 ignition (standing pilot) or Figure 22 for  

 

 intermittent ignition (EI).

16. Draw off one quart of water from bottom gauge  

 glass fitting and discard.  Draw off another quart  

 sample and if this sample is not clear, repeat the  

 cycle of draining the boiler and return main and  

 refilling the boiler until sample is clear.  

Summary of Contents for Classic CGS-A Series

Page 1: ... the boiler INSTALLATION OPERATING AND SERVICE INSTRUCTIONS Classic CGS A Series GAS BOILER n o n o i t a m r o f n i g n i k e e s n e h W r o t c a r t n o c g n i t a e h r u o y l l a c r e l i o b o t s r i a p e r r o e c i v r e s r o F l e b a L g n i t a R n o n w o h s s a r e b m u N l a i r e S d n a r e b m u N l e d o M r e l i o B e d i v o r p r e l i o b r e b m u N l e d o M r e ...

Page 2: ...O N n o i t a l l a t s n i n o s n o i t c u r t s n i l a i c e p s s e t a c i d n I e r a h c i h w e c n a n e t n i a m r o n o i t a r e p o y r u j n i l a n o s r e p o t d e t a l e r t o n t u b t n a t r o p m i s d r a z a h N O I T U A C n o i t a u t i s s u o d r a z a h y l l a i t n e t o p a s e t a c i d n I n i t l u s e r y a m d e d i o v a t o n f i h c i h w y t r e p o r ...

Page 3: ...pment B Installation must conform to the requirements of the authority having jurisdiction In the absence of such requirements installation must conform to National Fuel Gas Code NFPA 54 ANSI Z223 1 Where required by the authority having jurisdiction the installation must conform to the Standard for Controls and Safety Devices for Automatically Fired Boilers ANSI ASME CSD 1 C Boiler is design cert...

Page 4: ...ight construction adequate combustion and ventilation air is normally provided by fresh air infiltration through cracks around windows and doors 6 For boiler located within unconfined space in building of unusually tight construction or within confined space provide outdoor air through two permanent openings which communicate directly or by duct with the outdoors or spaces crawl or attic freely co...

Page 5: ... materials in distribution system Eliminate oxygen contamination by repairing system leaks repairing fittings and using nonpermeable materials in distribution system II Unpack Boiler Figure 3 Special Base Installation B Boiler equipped with McDonnell Miller 67 Low Water Cutoff Only Assemble gauge glass and low water cutoff as shown in Figure 5 Follow instructions packed with low water cutoff 1 Aff...

Page 6: ...a T e z i S e s o p r u P A 2 y l p p u S d n o c e S l a n o i t p O d e g g u l P 0 7 0 3 y l p p u S d n o c e S 0 8 B o t d e h s u b e g u a G e r u s s e r P C O C W L t a o l F s s a l G e g u a G D 2 d r a d n a t S n r u t e R E e v l a V y t e f a S F 2 e v l a V n i a r D e t a n r e t l A n r u t e R G 2 y l p p u S H t i m i L K f f o t u C r e t a W w o L e b o r P O C W L 7 6 r e l ...

Page 7: ... Figure 7 Recommended Boiler Piping for Gravity Return ...

Page 8: ...ons other than those listed above refer to National Fuel Gas Code NFPA 54 ANSI Z223 1 or size system using standard engineering methods acceptable to authority having jurisdiction B Connect boiler gas valve to gas supply system 1 Use methods and materials in accordance with local plumbing codes and requirements of gas supplier In absence of such requirements follow National Fuel Gas Code NFPA 54 A...

Page 9: ... u s s e r P c w h c n i 3 0 p o r D e r u s s e r P c w h c n i 5 0 1 1 1 1 0 1 2 3 1 8 7 2 0 2 5 0 5 0 1 5 7 1 0 6 3 0 8 6 0 0 4 1 0 2 2 9 0 9 1 0 5 3 0 3 7 0 2 1 0 5 2 5 6 4 0 5 9 0 3 3 7 2 5 1 5 8 2 0 9 5 7 9 0 0 2 5 7 3 0 7 7 0 4 3 6 0 3 1 5 4 2 0 0 5 2 8 0 7 1 0 2 3 0 6 6 0 5 6 5 5 1 1 5 1 2 0 4 4 3 7 1 5 1 5 8 2 0 8 5 0 6 0 5 5 0 1 5 9 1 0 0 4 6 6 8 3 1 0 6 2 0 3 5 0 7 6 4 6 9 0 8 1 0 7 3 1...

Page 10: ...Install Draft Hood without modification on outlet of flue collector See Figure 1 Secure with sheet metal screws G N I N R A W y n a e c a l p r o d o o h t f a r d r e l i o b r e t l a t o n o D e h t n i r e p m a d d e v o r p p a n o n r o n o i t c u r t s b o e g a l l i p s s a g e u l F m e t s y s t n e v r o g n i h c e e r b e m o c e b l l i w n o i t a c i f i t r e c A G A r u c c o ...

Page 11: ... Damper Installation G N I N R A W s i h t e s u d n a l l a t s n i y l r e p o r p o t e r u l i a F y t r e p o r p n i t l u s e r y a m h c t i w S t n e V d e k c o l B e f i l f o s s o l r o y r u j n i l a n o s r e p e g a m a d E Install Vent Damper See Figure 11 1 Open Vent Damper Carton and remove Installation Instructions Read Installation Instructions thoroughly before proceeding E ...

Page 12: ...e the other appliances remaining connected to the common venting system are not in operation a Seal any unused openings in the common venting system b Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condition c Insofar as is practical close all building do...

Page 13: ... 13 Vent Damper Schematic Wiring Diagram Table 8 Wiring Diagrams F Wire boiler Boiler is rated for 120 VAC 60 hertz less than 12 amperes Provide individual branch circuit with fused disconnect Connect to black and white wires and green ground screw Install Transformer on Junction Box G Vent Damper Sequence of Operation See Figure 13 1 Vent Damper continuously powered at Terminal 1 2 Call for heat ...

Page 14: ... flame and causes gas valve to turn off main burner and pilot burner gas flow should pilot burner flame extinguish Vent Damper remains open with call for heat H Sequence of Operation Continuous Ignition Standing Pilot 1 Normal Operation a Thermostat calls for heat Vent Damper opens b Gas Valve energized allowing main gas flow and ignition of Main Burners c Call for heat ends Gas Valve de energized...

Page 15: ...t for one minute Vent Damper remains open with call for heat For Electronic Ignition Troubleshooting Guide see Pages 26 27 I Sequence of Operation with Intermittent Ignition EI 1 Normal Operation a Thermostat calls for heat Vent Damper opens b Ignition Module energized Pilot Valve opens Igniter energized to ignite Pilot Burner c Sensor proves presence of pilot flame Main Valve opens and ignites Ma...

Page 16: ...enses pilot flame and causes gas valve to turn off main burner and pilot burner gas flow should pilot burner flame extinguish Vent Damper remains open with call for heat L Sequence of Operation Continuous Ignition Standing Pilot 1 Normal Operation a Thermostat calls for heat Vent Damper opens b Gas Valve energized allowing main gas flow and ignition of Main Burners c Call for heat ends Gas Valve d...

Page 17: ...blockage must be corrected by trained and skilled personnel from a qualified service agency before resetting switch d Flame Roll out Switch Automatically interrupts boiler operation when flames or excessive heat are present in vestibule Vent Damper remains open with call for heat Control is single use device If flame roll out switch is activated do not attempt to place boiler in operation The sour...

Page 18: ... piping and connections between Gas Valve and Manifold orifices and pilot tubing while boiler is operating Locate leaks using approved combustible gas detector soap and water or similar nonflammable solution Do not use matches candles open flames or other ignition source Figure 18 Pilot Burner Flame Continuous Ignition H Check pilot burner flame 1 Continuous Ignition standing pilot See Figure 18 P...

Page 19: ...r p e r a c t e t s u d l l a w r e n r u b e h t s n o i t i d n o c e s e h t r e d n u d e t a r e p o d n a d e n a e l c e b t s u m s t r o p d n a r o i r e t n i n o i t a r e p o r e p o r p e r u s n i o t y l i a d d e t c e p s n i s d n o c e S e n O r o f n o i t u l o v e R l a i D r e t e M s a G f o e z i S f l a H e n O t F u C e n O t F u C o w T t F u C e v i F t F u C 0 3 0 6 ...

Page 20: ...pilot or Figure 22 for intermittent ignition EI Adjust thermostat to normal setting 4 Determine Input Rate Multiply gas flow rate by gas heating value 5 Compare measured input rate to input rate listed on rating label a Boiler must not be overfired Reduce input rate by decreasing manifold pressure Do not reduce more than 0 3 inch w c If boiler is still overfired contact New Yorker Boiler Company f...

Page 21: ...ot or Figure 22 for intermittent ignition EI Remove manometer 5 Follow Lighting or Operating Instructions to place boiler in operation See Figure 21 for continuous ignition standing pilot or Figure 22 for intermittent ignition EI Adjust thermostat to normal setting Q Clean Heating System Oil from new piping connections and sediment in existing piping must be removed from the system to prevent unst...

Page 22: ...e boiler in operation See Figure 21 for continuous ignition standing pilot or Figure 22 for intermittent ignition EI 3 Operate boiler at this water level for at least 30 minutes after the condensate begins to run hot 4 Follow instructions TO TURN OFF GAS TO APPLIANCE See Figure 21 for continuous ignition standing pilot or Figure 22 for intermittent ignition EI 5 Close all radiator valves Remove al...

Page 23: ...ready to be put into service U Combustion Chamber Burn off 1 The mineral wool combustion chamber panels contain a cornstarch based binder that must be burned out a installation to prevent odors during subsequent boiler operation 2 Ventilate the boiler room set the high limit to its maximum setting set the thermostat to call for heat Allow the boiler to fire for at least an hour or until the odor f...

Page 24: ...r Cutoff McDonnell Miller 67 Only 1 Weekly or more frequently if necessary Open blow off valve to flush sediment chamber Follow instructions on Blow Down Card affixed to Jacket adjacent to low water cutoff 2 Annual Dismantle to extent necessary to remove obstructions and insure proper function of working parts a Inspect connecting lines to boiler for accumulation of mud and scale Clean as necessar...

Page 25: ... c Disconnect Flame Rollout Switch wires d Remove Burner Access Panel e Lift front of burner to clear orifice and lift burner out Burner which holds pilot can only be removed by lifting at a 45 angle after burner adjacent to its right is removed 2 Brush top of burners with a soft bristle brush See Figure 24 Vacuum burners 3 Check orifices Drilled passageways must be free of lint or dirt Figure 25 ...

Page 26: ...26 ELECTRONIC IGNITION TROUBLE SHOOTING GUIDE ...

Page 27: ...27 ...

Page 28: ... n a C 3 0 2 1 1 1 6 1 4 0 2 1 1 1 6 1 5 0 2 1 1 1 6 1 6 0 2 1 1 1 6 1 7 0 2 1 1 1 6 1 8 0 2 1 1 1 6 1 8 8 x 2 x 2 1 p i r t S g n i l a e S t l e f a r e C e s a B o t y l b m e s s A n o i t c e S 1 7 0 7 1 0 2 7 1 1 1 1 1 1 t e k c a r B e c i f i r O d e t t o l S w r e n r u B n i a M 9 1 1 6 3 2 8 3 4 6 9 1 1 4 1 d n a t e k c a r B t o l i P 0 5 3 Q 0 7 h t i w r e n r u B n i a M n o i t i...

Page 29: ...8 R V l l e w y e n o H e v l a V s a G 3 8 1 0 6 6 1 8 1 1 e n a p o r P P L 0 4 0 6 C 0 0 3 8 R V l l e w y e n o H e v l a V s a G 3 4 2 0 6 6 1 8 1 1 1 1 e n a p o r P P L 8 4 5 4 C 0 0 3 8 R V l l e w y e n o H e v l a V s a G 4 4 2 0 6 6 1 8 1 1 6 6 9 1 A 9 0 3 Q l l e w y e n o H 6 3 e l p u o c o m r e h T 4 0 0 6 3 2 8 1 8 8 9 1 A 9 0 3 Q l l e w y e n o H 0 3 e l p u o c o m r e h T 4 2 ...

Page 30: ...e m r o f s n a r T 1 0 0 1 1 0 7 1 1 1 1 1 1 h c t i w S t u o l l o R e m a l F 4 4 0 0 6 1 0 8 1 1 1 1 1 1 y l b m e s s A t n e m e c a l p e R h c t i w S t n e V d e k c o l B 6 6 0 6 1 0 6 1 1 1 1 1 1 r e t a W w o L o t u C l o r t n o C d n a e b o r P 0 0 4 5 4 l e v e l o r d y H f f 5 2 6 0 6 1 0 8 1 1 1 1 1 1 C r e t a W w o L o t u 2 0 8 S P r e l l i M l l e n n o D c M f f l o r t ...

Page 31: ... Long sleeved loose fitting clothing 3 Gloves 4 Eye Protection Take steps to assure adequate ventilation Wash all exposed body areas gently with soap and water after contact Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes Discard used RCF components by sealing in an airtight plastic bag RCF and crystalline silica are not clas...

Page 32: ...associated controls 6 Geographic Limitations These warranties apply only to boilers installed within the 48 contiguous United States 7 Installation Requirements In order for these warranties to be effective a The boiler must be installed in a single or two family residential dw This warranty does not apply to boilers installed in apart elling ments or for commercial or industrial applications b Th...

Reviews: