• Automatic unattended local shutdown 
• Special software modules to close and save open MS-Office documents. 
• Compatible for all optional modules like UPSDIALER, SNMP adapters, 

Temperature sensors, etc.The UPS-Management Software is a client-/server-

application for networks and local workstations. Basically Wavemon consists of two parts: the 
server-module of the UPS-Management Software is UPSMAN, which communicates via RS-232 
cable with the UPS. Working as a background process the UPSMAN collects messages, received 
from the UPS. The UPSMAN interprets received messages and makes them available to the client-
module UPSMON and to any SNMP-based management station. 

When UPSMAN detects voltage variations or a power failure it can execute various so called 
system „event routines“, which for example may shutdown the server or send warning to connected 
users. These system event routines which are a part of the UPS-Management Software can be 
adjusted to your demands. 

The UPS management software includes with every serial number the licence for using the UPS 
service on one server with one UPS and an unlimited numbers of connected WINDOWS 
workstations. When operating with two or more servers a licence for every additional server is 
required. It doesn’t matter if the UPS service runs at that location or if the server is halted by a UPS 
service via remote command. The same regulations are applicable to the use of remote 
send/receive modules RCCMD and multiserver shutdown under NT, UNIX and other operating 
systems. The service programs are generally delivered as a single-licence. To use a single CD 
ROM to shutdown multiple servers you have to purchase additional CD license keys. 

Parallel/redundant UPS systems are also manageable by the software. 

The main principle is: let introduce a shutdown of a Server only when strictly necessary. A correct 
Parallel Handling has therefore to manage a parallel system as a whole and always considering 
redundancy. Following statements apply: 

- Every alarm on any unit is immediately notified, but … 
- … a reaction to a severe fault is introduced only when the minimum number of UPS –Modules 

necessary to supply the load exhibits an alarming situation. 

- The real Battery autonomy time of the (whole) parallel system is computed continuously. 
- Maintenance on a redundant unit may be executed without annoyance to the management system 

(supervisor). 

In order to be managed, a NEWAVE UPS can be integrated into a network in two ways: 

1. By means of the server which is being powered by the UPS and is integrated in the network. In 
most of the cases the server is used as sub-agent and you only need the Wavemon software 
without any SNMP Adapter. You need a standard serial connection between the RS232 SMART 
port of the UPS and the RS232 port of the computer/server. 

2. In some situations it is preferable to interface the network via an SNMP adapter. By this way up 
to 50 computers can be shut down in a RCCMD environment. RCCMD (Remote Console 
Command) is an additional software module, which can be triggered by the SNMP device to 
executes a command (typically a shutdown command) on a remote system. 

Summary of Contents for 1000-3000VA

Page 1: ...User Manual 1000 3000VA single phase In Output Intelligent True On Line Uninterruptible Power Supply UPS For Corporate IT User Installation Guide...

Page 2: ...Intelligent True On Line Uninterruptible Power Supply UPS For Corporate IT User Installation Guide...

Page 3: ...1 UPS System Block Diagram 20 5 2 When Utility is Normal 21 5 3 When Utility is Abnormal Absent 21 5 4 Overload Condition 22 5 5 Inverter Failure 23 5 6 Inverter Internal Over temperature 23 5 7 Inver...

Page 4: ...0 3 2 Selecting Installation Position 36 10 3 3 Installation Instructions 37 10 3 4 Rack Mount installation 39 10 3 5 Storage Instruction 42 10 3 6 Replacing the Battery 42 10 3 7 Specifications 43 10...

Page 5: ...hould be recharged every 2 3 months if not in use to prevent battery self discharge The battery can be recharged when the UPS is connected to the utility suppl 6 Always switch off the UPS and disconne...

Page 6: ...re enables the UPS for integration even in the most difficult of environment with space constraints 2 This UPS is equipped with fully digitalized control logic for greater functionality and enhanced h...

Page 7: ...9 Site wiring fault LED Red LED illuminated indicates Live Neutral lines are connected wrongly or High Neutral Ground voltage 10 Battery Bad Weak LED Red LED illuminated indicates low battery power o...

Page 8: ...Dry Contact Signal inputs 4 Communication Card Options Slot 5 External Battery Connector 6 AC power connection socket 7 AC Outlets 8 Two programmable outlets 9 Utility Input fuse holder 10 Cooling Fa...

Page 9: ...ct Normal CF50 CF60 Mode 4 Fine turning of Output Voltage Regulation from 0 3 5 Bypass Sensitivity Select Sensitivity Low Sensitivity High 6 Synchronizing Select 3Hz 1Hz Inverter Freq synchronizing ra...

Page 10: ...al loads connected to the UPS 3 Outlet Turn On After AC Recovered select this option to automatically enable the outlet within the specified time after the utility is restored 4 Outlet Turn Off When B...

Page 11: ...hipment Notify the forwarder and dealer if there is damage The packaging is recyclable save it for reuse or dispose of it properly Remove the UPS from the carton box Check the package contents Standar...

Page 12: ...istance clearance from the rear panel of the UPS to avoid any obstructions 2 Do not block the air flow to the ventilation louvers of the unit 3 Please ensure the installation site is free from excessi...

Page 13: ...4 3 Tower Configuration Setup Step 1 Step 2...

Page 14: ...Step 3 Step 4...

Page 15: ...4 4 Rack Mount Configuration Setup Step 3 Step 4 Step 5...

Page 16: ...Step 6 Step 7...

Page 17: ...ndicating the UPS is in Battery Mode Connect a non critical load to the UPS outlets to confirm if the Battery is supplying power Repeat the test by switching on off the AC power source to ensure the U...

Page 18: ...ts or abnormal conditions The LED will automatically lights off 30 sec after the successful self test 4 5 5 Status Alarm Buzzer The following table helps to define some of the common UPS statuses with...

Page 19: ...4 5 6 Battery Replacement Step 1 Step 2 Step 3...

Page 20: ...Step 4...

Page 21: ...onditions indications Utility Normal Rectifier convert AC to DC battery LEDs charging Inverter convert DC to AC and supply to loads with clean stable power remain illuminated Utility Abnormal Rectifie...

Page 22: ...delay and turn off the charger and AC DC converter The inverter revert DC to AC to supply energy to the output load connected without interruption The LED will be illuminated 2 When Utility is back to...

Page 23: ...is equipped with electronics overload protection feature as standard If the UPS loading is 105 120 of its capacity it will switch to bypass mode in 30 seconds to protect the Inverter If overload cond...

Page 24: ...ting after the short circuit condition is eliminated 5 6 Inverter Internal Over temperature If the UPS experiences internal over temperature when Utility is normal it will switch to bypass loop The UP...

Page 25: ...n cables due to broken cable insulator Replace the cables in necessary 3 Er11 UPS Over Temperature 3 Remove any objects obstructing the ventilation louvers Verify if the cooling fans are working prope...

Page 26: ...UPS and call for service UPS is unable to Check that the battery connectors are provide backup fully engaged Allow the battery to power source recharge if the batter is weak If problem persist after...

Page 27: ...onnect Er28 Bypass overload Er31 EEPROM s data not conform to the Jumper Setting 7 Bundle Software Installation Guide 7 1 Hardware Installation 1 Connect the male connector of RS232 USB cable to the U...

Page 28: ...system NEWAVE has found it important to have a complete solution for its UPS and is able to offer a wide range of monitoring remote controls for assuring the maximum protection degree to the NEWAVE cu...

Page 29: ...server shutdown under NT UNIX and other operating systems The service programs are generally delivered as a single licence To use a single CD ROM to shutdown multiple servers you have to purchase addi...

Page 30: ...residual battery autonomy time downtime or by a countdown timer which is started at the beginning of the alarm A shut down is therefore possible without extra input from the operator and is fully sof...

Page 31: ...are Unix Linux please contact your local dealer for suitable software All the communication ports including optional cards can be active use simultaneously to monitor the UPS status However only 1 com...

Page 32: ...ion Cards The UPS rear panel is equipped with a ready plug and play optional communication card slot to accommodate either a AS400 Dry Contact card or SNMP Web card These optional communication cards...

Page 33: ...wn UPS positive signal Pin 10 Shutdown UPS negative signal To Shutdown the UPS supply a DC voltage of between 5 5V 25V to Pin 9 use as terminal and Pin 10 use as terminal 9 2 SNMP Cards Both SNMP card...

Page 34: ...ty environment The warranty for this battery bank will be void if water or other liquid is spilt or poured directly onto the battery bank Similarly we do not warrant any damage to the battery bank if...

Page 35: ...erminal of the 2nd or next battery bank connected 3 UPS BAT To the UPS DC terminal or the next battery bank 4 DC Breaker 1 Battery Over current Protection Breaker 2 To easy swappable battery please pu...

Page 36: ...installation Retain the packing material for future use 10 3 1 Unpacking 1 Take the battery bank out of the PE foam 2 Remove the packing materials Note The battery bank module is approx 12 5 50 kgs be...

Page 37: ...the rear panel of the battery bank from the wall or other obstructions 2 Do not block the air flow to the ventilation openings of the unit 3 Please ensure the installation site environmental conditio...

Page 38: ...10 3 3 Installation Instructions Tower installation Stand alone unit Step 1 Step 2...

Page 39: ...Use with UPS Step 1 Step 2...

Page 40: ...10 3 4 Rack Mount installation Step 1 Step 2...

Page 41: ...Step 3 Step 4...

Page 42: ...Second Battery First Battery Bank UPS Connect DC Cable...

Page 43: ...ate 15 to 30 C 5 to 86 F the batteries should be charged for 12 hours every 6 months by plugging the UPS power cord into the wall receptacle Repeat this every 3 months under high temperature 30 to 45...

Page 44: ...Step 3 Step 4 10 3 7 Specifications...

Page 45: ...10 3 8 Recycling the Used battery Contact your local recycling or hazardous waste center for information on proper disposal of the used battery...

Page 46: ...11 Technical Specifications...

Page 47: ...TECHNICAL SPECIFICATIONS POWERVARIO Intelligent True On Line Uninterruptible Power Supply UPS For Corporate IT User Installation Guide...

Page 48: ...ons 3 1 1 VA Rating 3 1 2 Input 3 1 3 Output 3 1 4 Battery System 4 1 5 Transfer Time 4 1 6 Front Panel 4 1 7 Protection 4 1 8 Audible Alarm 5 1 9 Physical 5 1 10 Environmental 5 1 11 Interface 5 1 12...

Page 49: ...60 Hz auto select 5Hz Phase Single phase with ground PF 0 99 at full rated linear load Typical Transfer Time 0 ms AC Leakage current 230V 3 5mA Surge Protection 230V 300 joules Model PVO1000 PVO2000 P...

Page 50: ...C to DC Zero Inverter to Bypass 2 5ms Typical Zero DC Start Yes Self Diagnostics Upon Power on and Software Control Model PVO1000 PVO2000 PVO3000 LED Load Level Battery Level Battery Mode Normal Mode...

Page 51: ...VO1000 PVO2000 PVO3000 Battery Mode Sounding once every 1 5 seconds Low Battery Sounding once every 0 2 seconds Overload Sounding once every 3 second Fault Continuously Sounding or Sounding once every...

Page 52: ...cation Model PVO1000 PVO2000 PVO3000 Safety IEC EN 62040 1 1 IEC 60950 1 Performance IEC EN 62040 3 EMC EN50091 2 IEC 62040 2 class A IEC 61000 4 2 3 4 6 8 11 IEC 61000 3 2 3 Markings CE cUL FCC addit...