1.1.4 ENVIRONMENTAL CONSIDERATIONS
The UPS must be installed according to the recommendations in this manual. To operate the UPS at peak
efficiency, your installation site should meet the environmental parameters outlined in this manual. Excessive
amount of dust in the operating environment of UPS may cause damage or lead to malfunction. The UPS should
be always protected from the outside weather and sunshine. If you intend to operate the system at an altitude
higher than 1000 meters, contact your local sales or service office for important information about high altitude
operation. The operating environment must meet the weight, airflow, size and clearance requirements specified in
the technical datasheet.
Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or in
an environment exceeding the specification.
The basic environmental requirements of the UPS system are:
•
Ambient Temperature Range:
0 to +40˚C
(32 – 104˚F)
•
Recommended Operating Range:
+20 to +25˚C
(68 – 77˚F)
•
Maximum Relative Humidity:
95% (non-condensing)
The UPS cabinet uses forced air cooling to regulate internal component temperature. Air inlets are in the bottom
sides and front of the cabinet, and outlets in the rear of the cabinet. You must allow clearance in back of the
cabinet for proper air circulation. Refer to
Section 1, 4.2.2 POSITIONING
for clearance requirements.
1.1.5 DECLARATION OF SAFETY CONFORMITY AND CE MARKING
The product has the CE marking in compliance with the following European directives:
•
Low Voltage Directive:
2006/95/EC
•
EMC Directive:
2004/108/EC
Declaration of conformity with UPS harmonized standards and directives EN 62040-1 (Safety) and EN 62040-2
(EMC) is enclosed in Annexe (1)
Safety
IEC/EN 62040-1, IEC/EN 60950-1
Electromagnetic Compatibility
IEC/EN 62040-2, IEC/EN61000-3-2,
IEC/EN61000-6-2,
EMC Classification for
10kVA
15-50kVA
Emission Class
C2
C3
Immunity Class
C3
Performance
IEC/EN62040-3
Product certification
CE
Degree of protection
IP 20
1.1.6 INQUIRIES
Address inquiries about the UPS and battery cabinet to the local office or agent authorized by the manufacturer.
Please note the type code and the serial number of the equipment and contact your nearest agent authorized by
the manufacturer (
www.newavenergy.com
under Resellers).
The Code and the serial no. are shown on the nameplate see
Section 1, 1.3.4 Nameplate