Newave_OPM_PV11_PV31 _GB_250805.doc Installation
Page 13
Elements:
FA1 Rectifier
Line
Fuse
FA2 Bypass
Line
Fuse
FA3 Battery
Fuse
IA1 Maintenance
Bypass
IA2 Output
Switch
JD1
Smart Port-RS232 (SUB-D9P/F)
X1-X21 Dry Port-volt-free contacts on
terminal block (see chapter 3.8.2)
In/Out Terminal Block
+ N -
Only for
external
battery
FA1
IA1 IA2 FA2
FA3
X1-X21
JD1
SNMP
FA1 (A)
FA2 (A)
FA3 (A)
7,5kVA
50 A
(14x51)
ultrafast
50 A
(14x51)
GL/GC
32 A
(10x38)
ultrafast
10kVA 50
A
(14x51)
ultrafast
50 A
(14x51)
GL/GC
32 A
(10x38)
ultrafast
12kVA 50
A
(14x51)
ultrafast
50 A
(14x51)
GL/GC
32 A
(10x38)
ultrafast
Figure 1
Connection of UPS POWERVALUE 7.5, 10 and 12kVA with single phase input mains supply. Output
Load connection terminals and connection of possible optional battery cabinet (SINGLE INPUT FEED).
PowerValue
TM
11
Cabinet “A” rear View / Cabinet “B and C ” front View
Output
(To Load)
3L1 3N PE
Mains Input
(Single Feed)
1N 1L1 PE
Separate Bypass
(For Dual
Feed)
PE 2L1 2N
Cabinet A
Cabinet B and C
SNMP
JD1
X1-
X21
FA1
IA1 IA2 FA2
FA3
Note: the number of fans depend on
the power of the UPS.