Newave_OPM_PV11_PV31 _GB_250805.doc Troubleshooting
Page 37
6 Troubleshooting
6.1 ALARMS
In the event of an alarm condition the red LED-Indicator “Alarm” and the audible alarm will turn on.
In this case proceed as follows:
1. Silence the audible alarm by pressing the button "Reset".
2. Identify the cause of the alarm condition by means of the EVENT LOG in the MAIN menu.
3. In case of doubts please contact the nearest Service centre.
4. Fault identification and rectification information is given on the following pages.
6.2 MENU, COMMANDS, EVENT LOG, MEASUREMENTS,
In Chapter 4 there is a detailed description of the Menu, Commands, Event Log and Measurements
that can be operated and displayed on the LCD. The List of Alarms and Messages are shown in the
Annexe.
6.3 FAULT IDENTIFICATION AND RECTIFICATION
The major alarm conditions that will be encountered are:
Alarm Condition
Meaning
Suggested Solution
UPS FAULT
There is a fault in the UPS and
therefore normal operation cannot
be guaranteed
Call the authorised service centre for
assistance
MAINS BYP/RECT
FAULT
Mains power supply is outside
prescribed tolerance
The input power to UPS is too low or missing.
If site power appears to be OK, check the input
circuit breakers etc. supplying the UPS
OUTPUT SHORT
There is a short circuit at the output
of UPS (on load side)
Check all output connections and repair as
required.
OVERLOAD
Load exceeds the UPS rated power
Identify which piece of equipment is causing
the overload and remove it from the UPS.
Do not connect laser printers, photocopiers,
electric heaters, kettles etc. to the UPS
OVERTEMPERATURE
UPS temperature has exceeded the
allowed value
Check the ambient temperature of the UPS is
less than 30° C.
If the ambient temperature is normal call the
authorised service centre for assistance.
BATTERY CHARGER
OFF
The attached battery and the
battery charger set-up do not
correspond or battery charger fault
Call the authorised service centre for
assistance.
INVERTER FAULT
Inverter is faulty.
Call the authorised service centre for
assistance.
SYNCHRON FAULT
The inverter and mains are not
synchronised.
The frequency of the input voltage to the UPS
is outside operational limits and the UPS static
bypass has been temporarily disabled.
BATTERY IN
DISCHARGE
Battery is near end of autonomy
Shutdown load connected to UPS before the
UPS switches itself off to protect its batteries
MANUAL BYP IS
CLOSED
Maintenance Bypass closed. Load
supplied by mains
This alarm is only displayed if the UPS is on
Maintenance Bypass