3.4 STORAGE
3.4.1 UPS
If you plan to store the UPS prior to use, keep the UPS unpacked in a dry, clean and cool storage
room with an ambient temperature between (+5 °C to +40°C) and humidity of less than 90%.
If the packing container is removed protect the UPS from dust.
3.4.2 Battery
The battery life depends very much on the ambient temperature.
It is therefore important not to store the battery longer than 6 months at 20°C, 3 months at 30°C and 2
months at 35°C storage temperature without a battery recharge.
For longer-term storage make sure that the battery is fully recharged every 6 months.
SEALED BATTERIES MUST NEVER BE STORED IN A DISCHARGED OR PARTIALLY
DISCHARGED STATE.
EXTREME TEMPERATURE, UNDER- AND OVERCHARGE AND OVERDISCHARGE WILL
DESTROY BATTERIES!
Before and after storing, charge the battery.
Always store the batteries in a dry, clean, cool environment in their original packaging.
If the packing container is removed protect the batteries from dust and humidity.
3.5 POSITIONING
The
PowerValue
TM
is a compact and light UPS and can easily be moved to the final position.
All parts of the
PowerValue
TM
are accessible from the front and rear
making it a service-friendly and
maintenance-friendly UPS.
The UPS should be located where:
•
Humidity and temperature are within prescribed limits;
•
Fire protection standards are respected;
•
Cabling can be performed easily;
•
Available front accessibility for service or periodic maintenance;
•
Requested air cooling flow should be granted;
•
The air conditioning system should have sufficient capacity;
•
Dust or corrosive/explosive gases must be absent;
•
The place is vibration free;
•
Minimum 10cm rear space is recommended for accessibility (see Figure 3.1 and 3.2);
•
Only front and rear access is necessary for service and maintenance.
Clearances
X
Clearances
X
X (Rear )
100mm
X (Rear )
100mm
Y (Right Side)
400mm
Y (Right Side)
400mm
NOTE:
Cabinet A and B
are provided with rollers and if on the installation side 1m longer cables are
foreseen the UPS can be moved to the front and serviced.
Cabinet C
needs left and right access of 400mm
Figure 3.1: UPS space recommendation
Figure 3.2: UPS + Battery cabinet space recommendation