16
• For CL115, 140, 155, 170, a minimum supply duct free area of 220, 220, 240, 260 sq. in. respectively, must be
maintained at all times during heating the cycle.
• For CL115, 140, 155, 170, a minimum return duct free area of 250, 250, 280, 300, sq. in. respectively, must be
maintained at all times during heating the cycle.
• A/C coils installed above heat exchanger should be located over oil section.
• A/C coils installed above heat exchanger should be located as high as possible and no less than 12 inches
above the top of the heat exchanger.
• A/C coils must not be located on return air side.
• Ensure condensate from coil does not drip onto heat exchanger surfaces.
• Condensate drip trays must be metal.
•
Ensure duct sizes are as specified in Installation, Operating and Service Manual.
•
Increased air flows may require more frequent air filter maintenance.
Emerson 3/4 h.p. Single Speed Belt Drive Motor: p/n 2020020
3-1/2” X 5/8” VS motor pulley: p/n 2240008.
Blower pulley, 7” X 3/4”: p/n 2240002.
41” Blower Belt: p/n 2240041.
Honeywell 8405A fan center transformer relay: p/n 2010015.
Honeywell 8285A fan center transformer relay: p/n 2010041.
Honeywell 8239B fan center transformer relay: p/n 2010059.
The unit must be installed in accordance with the National Warm Air Heating and Air Conditioning Association
Standards or generally accepted equivalent standards. Consult appropriate provincial, state, or local codes.
Regulations governing installation requirements may vary from the ones presented here
CONVERSION OF CL86 C & G TO 4 TONS A/C
• 1/2” HP Motor Recommended.
• Use existing motor pulley.
•
7” X 3/4” Blower Pulley Recommended (Standard is 8”).
•
39” X 1/2” Blower Belt required for 7” pulley.
• See A/C wiring diagram with Honeywell 8405A Relay (or equivalent).
• Install a By-Pass damper or blast as per sketch “Typical A/C Coil Installation”.
• A minimum supply duct free area of 180 square inches must be maintained at all times during heating the
cycle.
• A minimum return duct free area of 250 square inches must be maintained at all times during heating the
cycle.
• A/C coils installed above heat exchanger should be located over oil section.
• A/C coils installed above heat exchanger should be located as high as possible and no less than 12 inches
above the top of the heat exchanger.
• A/C coils must not be located on return air side.
• Ensure condensate from coil does not drip onto heat exchanger surfaces.
• Condensate drip trays must be metal.
•
Ensure duct sizes are as specified in Installation, Operating and Service Manual.
•
Increased air flows may require more frequent air filter maintenance.
Emerson 1/2 h.p. Single Speed Belt Drive Motor: p/n 2020003
Blower pulley, 7” X 3/4”: p/n 2240002.
39” X 1/2” Blower Belt: p/n 2240039.
Honeywell 8405A fan center transformer relay: p/n 2010015.
Honeywell 8285A fan center transformer relay: p/n 2010041.
Honeywell 8239B fan center transformer relay: p/n 2010059.
The unit must be installed in accordance with the National Warm Air Heating and Air Conditioning Association
Standards or generally accepted equivalent standards. Consult appropriate provincial, state, or local codes.
Regulations governing installation requirements may vary from the ones presented here
Summary of Contents for CL 115C
Page 7: ...7 Figure 7 FLUE PIPE CONNECTION MINIMUM INSTALLATION CLEARANCES...
Page 17: ...17 Figure 11 TYPICAL A C COIL INSTALLATION...
Page 18: ...18 Figure 12 WIRING DIAGRAM WITH AIR CONDITIONING...
Page 19: ...19 Figure 13 CL SERIES WIRING DIAGRAM...
Page 23: ...23 Figure 17 1E AERO PGB 220 370 GAS BURNER EXPLODED ASSLY...
Page 25: ...25 Figure 17 1G THERMO DISC MOUNTING ON BURNER PLATE...
Page 26: ...26 Figure 17 2A AERO BURNER EXPLODED ASSEMBLY...
Page 28: ...28 Figure 17 3A BECKETT BURNER EXPLODED ASSEMBLY...
Page 56: ...Figure 17 3A ASSEMBLAGE EXPLOD DU BR LEUR BECKETT...
Page 58: ...FIG 17 2A BR LEUR AERO ASSEMBLAGE CLAT...
Page 59: ...FIG 17 1G LE DISQUE DE THERMO MONTE SUR LA PLAQUE DE BR LEUR...
Page 64: ...FIG 13 C BLAGE DE LA S RIE CL...
Page 74: ...FIG 7 RACCORDEMENT DU TUYAU DE FUM E ET ESPACE LIBRE MINIMAL FIG 8 EMPLACEMENTS DES COMMANDES...