background image

THERMOSTAT LOCATION
For   central   heating   applications   a   room   thermostat   is   recommended   to   provide   automatic
temperature control and efficient operation.

The thermostat should be mounted on an inside partition wall clear of drapes, heaters, doors and the
effects of external windows.  Generally the thermostat is placed in the main living area.

The thermostat controls the output from the heater by activating the combustion air damper. When
the thermostat calls for heat the combustion air damper opens which allows the fire to build up to
maximum  temperature.  When the room reaches the desired temperature the thermostat closes the
combustion air damper allowing the fire to reduce to slow combustion.

SUPPLY DUCTWORK
The ductwork must be fabricated from non combustible material,  thermally insulated and designed
not   to   restrict  the  total   air  movement   to  the   outlets   and  in   no   case  start  off   less   than  350  mm
diameter.

It is essential that at least five 300 x 100 floor outlets be left open at all times otherwise the Newburn
will overheat which will cause damage to the heat exchanger.

The ductwork must be designed to recognised standards and installed by competent tradesperson
with experience in this field to ensure correct operation.

RETURN AIR DUCT
For maximum economy it is recommended that a minimum 350 mm diameter return air duct be
connected to  deliver  room  air back to  the  furnace for  reheating.    The  return air duct should be
insulated for noise absorption and thermal insulation and connected into the side or rear of the fan
compartment.
Return Air is best collected at low level from within the house.
(Note :  Return Air Grille not supplied with furnace).

ELECTRICAL REQUIREMENTS
The heater requires a power supply to operate the combustion air damper motor and supply air fan.
Power supply to be 240 volts/50HZ.

A dedicated hard wired connection is recommended to avoid inadvertent switching off or unplugging
as   may   occur   when   connected   to   a   general   power   outlet.     Ensure   the   power   supply   is   always
switched on prior to lighting the furnace.

It is important the room thermostat wiring circuit operates the combustion air damper only.  
Control   of   the   supply   air   fan   is   temperature   actuated   by   the   inbuilt   heat   exchanger   thermostat
(Honeywell fan/limit controller) which is mounted on the right front of the Newburn.
Ensure this is set on Auto mode (out).

3

Summary of Contents for Newburn

Page 1: ...WOODFIRED CENTRAL HEATING FURNACE INSTALLATION and OPERATION MANUAL METALFAB 125 WILSON ST BURNIE TASMANIA Telephone 03 6431 4766 Facsimile 03 6431 6811 Email sales newmansplumbing com au ...

Page 2: ...imum 50mm air space around the sides back and above the unit from combustible surfaces Also the unit should be installed on a level concrete slab of not less than 50 mm thickness FLUE INSTALLATIONS The flue must be 150 mm diameter of 0 6 mm stainless steel and all joints be sealed and lapped so that the lower section of flue is entered into the top section of the adjoining piece This will stop any...

Page 3: ...hanger The ductwork must be designed to recognised standards and installed by competent tradesperson with experience in this field to ensure correct operation RETURN AIR DUCT For maximum economy it is recommended that a minimum 350 mm diameter return air duct be connected to deliver room air back to the furnace for reheating The return air duct should be insulated for noise absorption and thermal ...

Page 4: ...larly that the combustion damper is working correctly and is unobstructed Check that the firebox door gasket is intact and sealing correctly Check the Return Air filter is clean or replace Clean out the ash regularly to prevent excessive build up and obstruction of combustion air intake Check the condition of the firebricks and baffle plates Inspect and clean your flue at least annually 4 ...

Page 5: ...5 ...

Page 6: ...or Ensure the room thermostat is turned up to set point 21 degrees RE FUELLING Crack open the firebox door for a few seconds before slowly opening fully Place wood in the firebox with care to avoid damage to firebrick lining Space pieces of wood to allow air circulation between them Close the firebox door tightly DO NOT OVERLOAD THE FIREBOX The wood should not be placed higher than halfway up the ...

Page 7: ...the switch on this controller is in the Auto out position In manual mode the fan will run continuously which is undesirable OVERNIGHT BURNING For successful overnight burning it is essential that there is a moderate fire already burning before loading the firebox with DRY wood Turn the room thermostat back to its lowest setting The furnace will now burn on low fire for approximately 6 to 8 hours I...

Page 8: ...n is critical to avoid overheating and damage to the firebox Ensure that the combustion air damper door is closed and un obstructed Do not open the fire box door in this situation If the door is opened the fire will build up and overheating will occur It is recommended that if the supply air fan fails turn the wall thermostat down to ensure that the combustion air damper remains closed off and the...

Page 9: ... to the other side of the firebox and then remove the remaining ash This ash will be very hot Handle and dispose of it carefully 4 Reposition the hot coals and unburned wood centrally and reset the fire with kindling and more wood Close the firebox door Reset thermostat to required temperature 5 Periodically allow the heater to go out in order to inspect the firebricks Cleaning should be done on a...

Page 10: ...10 ...

Page 11: ...11 ...

Page 12: ...12 ...

Page 13: ...r repairs to damage caused by burning coal or briquettes neglect abuse or accident No responsibility will be accepted for damage caused directly or indirectly by incorrect electrical wiring by incorrect installation or operation of the Heater The guarantee will not be recognised unless the form below is filled in and returned to the manufacturer WARRANTY REGISTRATION NEWBURN WOOD FIRED CENTRAL FUR...

Reviews: