Sense Type:

 Users can change the Sense Type according to operation condition. Three types 

for selection:

- UPS mode: The UPS can operate successfully with ups mode. The maximum transfer time is 

  5ms.

- Normal mode: The UPS can operate successfully with general line conditions. The maximum 

  transfer time is 20ms.

- Generator mode: This setting allows UPS to work with the fl uctuations caused by a generator 

  or noisy line. The maximum transfer time is 25ms.

Bat. Temp Comp:

 It adjusts the battery temperature compensated voltage to -2.5, -3.0, -3.5 or 

-4.0 mV/°C/Cell. The factory default setting is -3.0 mV/°C /Cell.

Ext. Fan:

 It indicates ambient temperature setting to switch on the external fan. The default 

value is 25°C (range 20 - 50°C)

Bat. Low Volt:

 Used to set the low battery warning voltage. For AC-UPS-48-1200, AC-

UPS-48-1500 & AC-UPS-48-2000, the resettable range is 42.0 ~ 55.0V. The default value is 46V. 

For AC-UPS-24-700 model, the resettable range is 21.0 ~ 27.5V. The default value is 23V.

Charger I:

 Used confi gure the charger current. There are 2, 4, 6, 8 or 10Amp for selection. The 

default value is 10A.

Backup Timer:

 Used to confi gure the warning time for backup time. This function is available 

only when timer is set in dry contact. The adjustable range is 0~480 min with 15-min 

increment of each click by pressing SCROLL button. The default value is 120min.

Default UPS:

 Restore factory settings of UPS.

Default SNMP:

 Restore factory settings of SNMP.

Test Timer:

 Used to defi ne the time of Self-Test. The adjustable range is 1~255min.

Set Date/Time:

 It indicates setting for date and time.

Password:

 The Password to access Setting and Control Menu can be changed here. Use the 

SCROLL key with ENTER keys to enter a correct Password. Re-entry is required if an error occurs 

when entering the password.

5.5.10 Control Menu

Press SCROLL button to switch desired option in Control menu and press ENTER button to confi rm new option. Pressing ESC 

button will return to default page.

Control page

Explanation

Starts the Self Test.

CAUTION: The unit must be in Normal, Boost or Buck Mode before starting the self-test.

Starts the dry contact test.

On: All dry contacts are energized. This action will be fi nished automatically after 1 minute.

Off: All dry contacts are ineffective. This action will be fi nished automatically after 1 minute.

Cancel: Cancel this test immediately.

Starts the external fan test.

On: The external fan has power from battery. This action will be fi nished automatically after 1 

minute.

Off: Cut off battery power. This action will be fi nished automatically after 1 minute.

Cancel: Cancel this test.
UPS output can be turned ON or OFF. This option is available when the UPS is in INV, Boost, 

Buck or Normal Mode.

       Bat Low Volt 

       Charger I

       Backup Timer 

       Default UPS

 

       Default SNMP       

       Test Timer

       Set Date/Time  

       Password     

 

 

Summary of Contents for AC UPS Series

Page 1: ...1 System Architecture 4 5 6 RS232 USB interface 15 3 2 UPS Module 4 5 7 Optional SNMP card 23 3 3 MBS Module Optional 5 6 SPECIFICATIONS 23 4 INSTALLATION 5 6 1 Line Mode Specifications 23 4 1 Unpack...

Page 2: ...in a risk of electric shock or fire 4 To reduce risk of electric shock disconnect all wirings before attempting any maintenance or cleaning Turning off the unit will not reduce this risk 5 CAUTION On...

Page 3: ...e Power Supply UPS System and optional Manual Bypass Switch AC UPS BP that provides backup power when the line is unqualified These components should be mounted inside an enclosure to provide protecti...

Page 4: ...ion 5 5 9 Internal Fan The fan is to cool down the inside temperature of the UPS and is easily replaced for maintenance GND This connector is the permanent ground of the UPS Battery Connector The batt...

Page 5: ...k The output power connects to the terminal block marked with AC OUT Switch This switch selects UPS or bypass output AC Output Breaker This circuit breaker labeled OUTPUT is a resettable protective th...

Page 6: ...ease immediately notify your carrier agent and the supplier who prepared your shipment 4 2 Mounting the UPS The UPS unit can be placed in a rack with no other parts needed It can be rack mounted or se...

Page 7: ...2 cables marked as UPS IN and UPS OUT Connect these cables from MBS to the respective connectors on the UPS 2 Connect the AC input wires to the AC input terminal blocks on the MBS Ensure proper polar...

Page 8: ...ed the UPS will transfer to line mode with the output LED ON to show UPS is running from utility power Note If the UPS keeps switching between inverter and line mode because of a noisy line the settin...

Page 9: ...P xxxxVA 9 O P P xxxxWatt 10 Load xxx 11 Mode xxxxx 12 InvEV xxxxx 13 InvTM xxxx xH 14 BukEV xxxxx 15 BukTM xxxx xH 16 BstEV xxxxx 17 BstTM xxxx xH 18 C1 Off or On C2 Off or On 19 C3 Off or On C4 Off...

Page 10: ...e 714 751 0488 Fax 714 372 7930 E Mail techservice newmarpower com PoweringTheNetwork com Figure 10 Setting and Control Page Pressing the ESC SCROLL and ENTER buttons to navigate through the menus and...

Page 11: ...voltage when output voltage achieves the user programmable preset limit Battery The unit automatically transfers to battery mode when input line power is unqualified or not present Batteries provide p...

Page 12: ...has been in battery mode The total time duration the unit has been in battery mode since the latest reset The number of times the unit has been in buck mode The total time duration the unit has been...

Page 13: ...ed as below User program Ext Alarm Ext Battery Alarm Ext Fan Failed Door Unlocked AVR Feature Enable or disable Buck and Boost function Factory default setting is enable Line Qualify Set AC recovery t...

Page 14: ...ustable range is 0 480 min with 15 min increment of each click by pressing SCROLL button The default value is 120min Default UPS Restore factory settings of UPS Default SNMP Restore factory settings o...

Page 15: ...ool HyperTerminal in Windows device can communicate with computer Follow below steps to step up HyperTerminal Step 1 The path of HyperTerminal communication tool is Programs Accessories Communications...

Page 16: ...Step 6 The Name of Unit Properties screen will pop up as shown in Figure 17 Click on the Settings tab Select all columns as below figure and click ASCII Setup button Figure 16 HyperTerminal Screen Fi...

Page 17: ...SETUP 60 CONTACT C1 Current Setting is ON BATT 0 Set to ON BATT 1 Set to LOW BATT 2 Set to TIMER 3 Set to ALARM 4 Set to FAULT 5 Set to OFF 6 Set to DISABLE 0 MAIN MENU 6 PROGRAMMABLE CONTACTS SETUP...

Page 18: ...nu numbers the line status the unit s output status and any faults or alarms that may be present Figure 20 Main Menu Screen BTS Manual Bypass Switch MBS UPS Model ID xxxxxxxxxxxxxx 0 MAIN MENU 1 Unit...

Page 19: ...re version Main Firmware Version Main board firmware version Hardware Version Hardware version IP Address UPS IP address Line Status Current Status Output Status Current Status Contact Status Current...

Page 20: ...e the latest RESET BUCK Event The number of times that BUCK function activates BUCK Timer Total time that the BUCK function activates since the latest RESET BOOST Event The number of times that BOOST...

Page 21: ...tions to factory default value 47 Set Date Adjust the date 48 Set Time Adjust the time 49 Change Password Change password The factory default password is 1111 Note The password can only be changed in...

Page 22: ...Mode Line to Battery 100VAC 88 120V AC 88V AC 88 120V AC 56 Boost Low When input voltage drops between Boost Back point and Boost Low point unit will transfer to Boost Mode only when AVR is enabled No...

Page 23: ...1 0 Nominal battery voltage 48V DC 24V DC Utility Voltage Waveform Sinusoidal utility or generator Utility qualify time setting 3 10 30 seconds adjustable Nominal Input Voltage 120V AC AVR function E...

Page 24: ...able Peak Efficiency 90 No Load Power Consumption 28W 48V DC 28W 24V DC THD Bat mode 3 Full resistive load Load crest factor 3 1 rated load Overload protection 5s 125 150 load 60s 110 125 load Output...

Page 25: ...AGM 28 2 56 4V DC 27 0 54 0V DC Battery Temperature Control Charging voltage is compensated according to battery temperature 2 5mV 3 0mV 3 5mV 4 0mV per cell per C compensated coefficient adjustable C...

Page 26: ...lace MBS UPS does not return back to Line mode Line power is missing Verify if power cord from UPS IN on MBS is properly connected to the AC input terminal blocks on UPS Verify if the UPS INPUT circui...

Page 27: ...bad temperature probe connected Only use factory supplied temperature probe reading approximately 15 000 OHMS 25 C 77 F LCD text is not readable UPS fault Return to repair center Password access is NO...

Page 28: ...e 24V DC 100Ah min Backup Time 24V DC 200Ah min AC UPS 24 700 10 1807 3613 20 858 1807 30 561 1205 40 378 869 50 306 703 60 253 581 70 197 442 80 155 383 90 137 337 100 121 294 9 WARRANTY AND FACTORY...

Reviews: