Sense Type:
Users can change the Sense Type according to operation condition. Three types
for selection:
- UPS mode: The UPS can operate successfully with ups mode. The maximum transfer time is
5ms.
- Normal mode: The UPS can operate successfully with general line conditions. The maximum
transfer time is 20ms.
- Generator mode: This setting allows UPS to work with the fl uctuations caused by a generator
or noisy line. The maximum transfer time is 25ms.
Bat. Temp Comp:
It adjusts the battery temperature compensated voltage to -2.5, -3.0, -3.5 or
-4.0 mV/°C/Cell. The factory default setting is -3.0 mV/°C /Cell.
Ext. Fan:
It indicates ambient temperature setting to switch on the external fan. The default
value is 25°C (range 20 - 50°C)
Bat. Low Volt:
Used to set the low battery warning voltage. For AC-UPS-48-1200, AC-
UPS-48-1500 & AC-UPS-48-2000, the resettable range is 42.0 ~ 55.0V. The default value is 46V.
For AC-UPS-24-700 model, the resettable range is 21.0 ~ 27.5V. The default value is 23V.
Charger I:
Used confi gure the charger current. There are 2, 4, 6, 8 or 10Amp for selection. The
default value is 10A.
Backup Timer:
Used to confi gure the warning time for backup time. This function is available
only when timer is set in dry contact. The adjustable range is 0~480 min with 15-min
increment of each click by pressing SCROLL button. The default value is 120min.
Default UPS:
Restore factory settings of UPS.
Default SNMP:
Restore factory settings of SNMP.
Test Timer:
Used to defi ne the time of Self-Test. The adjustable range is 1~255min.
Set Date/Time:
It indicates setting for date and time.
Password:
The Password to access Setting and Control Menu can be changed here. Use the
SCROLL key with ENTER keys to enter a correct Password. Re-entry is required if an error occurs
when entering the password.
5.5.10 Control Menu
Press SCROLL button to switch desired option in Control menu and press ENTER button to confi rm new option. Pressing ESC
button will return to default page.
Control page
Explanation
Starts the Self Test.
CAUTION: The unit must be in Normal, Boost or Buck Mode before starting the self-test.
Starts the dry contact test.
On: All dry contacts are energized. This action will be fi nished automatically after 1 minute.
Off: All dry contacts are ineffective. This action will be fi nished automatically after 1 minute.
Cancel: Cancel this test immediately.
Starts the external fan test.
On: The external fan has power from battery. This action will be fi nished automatically after 1
minute.
Off: Cut off battery power. This action will be fi nished automatically after 1 minute.
Cancel: Cancel this test.
UPS output can be turned ON or OFF. This option is available when the UPS is in INV, Boost,
Buck or Normal Mode.
Bat Low Volt
▼
Charger I
Backup Timer
Default UPS
Default SNMP
Test Timer
Set Date/Time
Password
▲