background image

5

6

SETTING OUTPUT SCALE AND OFFSET 

(continued)

Out 1

(OUTPUT 1)

Press ‘

RESET/ENTER

14) Display flashes 1st digit of
previous "

OUt 1

" value.

Press ‘

/MAX

’ & ‘ 

/MIN

15) Enter "

OUt 1

" value.

(Example 0000.00).

Press ‘

RESET/ENTER

16) Display advances to
"

REAd 2

" Reading 2 menu.

REAd 2

(READING 2)

Press ‘

RESET/ENTER

17) Display flashes 1st digit
of previous "

Reading 2

" value.

Press ‘

/MAX

’ & ‘ 

/MIN

18) Enter "

Reading 2

” value.

(Example 999999).

Press ‘

RESET/ENTER

19) Display advances to 
"

OUt 2

" Output 2 menu.

Out 2

(OUTPUT 2)

Press ‘

RESET/ENTER

20) Display flashes 1st digit of
previous "

OUt 2

" value.

Press ‘

/MAX

’ & ‘ 

/MIN

21) Enter "

OUt 2

" value.

(Example 0010.00).

Press ‘

RESET/ENTER

22) Display Display shows
"

StOREd

" stored message

momentarily and then advances
to the "

SP CNF

" SetPoint

Configuration menu.

The above example is for 0-10 V of the entire
range of the process input and analog output. For
0-20mA output you need to set "

MOdE

" to "

CURRNt

"

DC-Current output and "

OUt 2

" to 0020.00.

SPECIFICATIONS

Analog Output:

0-5 V, 1-5 V, 0-10 V, 0-20 mA, 4-20 mA level; 14-bit 
resolution; 0.1% accuracy; 6 msec step response.

Isolation

:

Power to Input / Analog, Comm, Ethernet, & Relay Output:
2500 Vac per 1 min. test
Relays to Inputs / Analog, Comm, & Ethernet Outputs:
2500 Vac per 1 min. test
Ethernet to Inputs / Analog Outputs:
1500 Vac per 1 min. test
Between Inputs / Analog & Comm Outputs:
500 Vac per 1 min. test

CONFIGURING THE OUTPUT 

(continued)

MOdE

ENTER OUTPUT MODE CONFIGURATION SUBMENU:

Press ‘

RESET/ENTER

5) Display shows " 

StOREd

"

stored message momentarily
and advances to "

MOdE

" to

allow users to select Output
type as Voltage (0-10Vdc or
Current (4-20mA-dc) source.

Press ‘

RESET/ENTER

6) Display flashes "

VOLt

"

(default) DC-Voltage output
option or previous selection
("

CURRNt

" DC-Current output).

Out.tyP

ENTER OUTPUT TYPE CONFIGURATION SUBMENU:

Press ‘

RESET/ENTER

7) Display shows "

OUt.tyP

"

Output Type Submenu.

Press ‘

RESET/ENTER

8) Display flashes "

UNF ILt

"

Unfiltered option or previous
selection.

Press ‘

/MAX

9) Scroll though and select
the following options for your
choice of setting:

"

UNF Ilt

": Transmits the unfiltered value of your signal input.

"

FILtRd

" : Transmits the filtered value of your signal input.

"

PEAk

" : Transmits the recorded Peak "

HI RdG

" Reading

value(s).

or "

VALLy

" : Transmits the recorded Valley"

LO RdG

"

Reading value(s).

SETTING OUTPUT SCALE AND OFFSET

OT.SC.OF

ENTER OUTPUT SCALE & OFFSET

CONFIGURATION SUBMENU:

REAd 1

(READING 1)

Press ‘

RESET/ENTER

10) Display shows "

REAd 1

"

Reading 1 menu.

Press ‘

RESET/ENTER

11) Display flashes 1st digit of
previous "

Reading 1

" value.

Press ‘

/MAX

’ & ‘ 

/MIN

12) Enter "

Reading 1

" value.

(Example 000000).

Press ‘

RESET/ENTER

13) Display advances to 
"

OUt 1

" Output 1 menu.

Ot.SC.OF

(Output Scale & Offset)

REAd  1

value

OUt  1

value

REAd  2

value

OUt  2

value

FILtRd

(Filtered)

OUt.tyP

(Output Type)

UNFILt

(Unfiltered)

PEAk

VALLy

TRADEMARK NOTICE:

,

,

newportUS.com

,

,

,

and the “Meter Bezel Design” are trademarks

of NEWPORT Electronics, Inc.

TM

®

NEWPORT

®

NEWPORT

®

This device is marked with the international caution symbol.   It is important to read the
Setup Guide  before  installing  or  commissioning  this  device  as  it  contains  important
information relating to safety and EMC.

WARNING:

These  products  are  not  designed  for  use  in,  and  should  not  be  used  for,  patient

connected applications.

It  is  the  policy  of  NEWPORT to  comply  with  all  worldwide  safety  and  EMC/EMI  regulations  that
apply. NEWPORT is constantly pursuing certification of its products to the European New Approach
Directives. NEWPORT will add the CE mark to every appropriate device upon certification.

The information contained in this document is believed to be correct, but NEWPORT Electronics,
Inc.  accepts  no  liability  for  any  errors  it  contains,  and  reserves  the  right  to  alter  specifications
without notice.

THENEW STANDARD FOR QUALITY

INF-B

Isolated Analog Output Option

For immediate technical or application assistance please call:

Newport Electronics, Inc.

2229 South Yale Street • Santa Ana, CA • 92704 • U.S.A.

TEL: (714) 540-4914 • FAX: (714) 546-3022

Toll Free: 1-800-639-7678 • http://www.newportUS.com  • e-mail:info@newportUS.com

ISO 9001 Certified

Newport Technologies, Inc.

976 Bergar • Laval (Quebec) • H7L 5A1 • Canada

TEL: (514) 335-3183 • FAX: (514) 856-6886

Toll Free: 1-800-639-7678 • http://www.newport.ca • e-mail:sales@newport.ca

Newport Electronics, Ltd.

One Omega Drive • River Bend Technology Centre

Northbank, Irlam • Manchester M44 5BD • United Kingdom

Tel: +44 161 777 6611 • FAX: +44 161 777 6622

Toll Free: 0800 488 488 • http://www.newportuk.co.uk • e-mail:sales@newportuk.co.uk

Newport Electronics B.V.

Postbus 8034 • 1180 LA Amstelveen • The Netherlands

TEL: +31 20 3472121 • FAX: +31 20 6434643

Toll Free: 0800 0993344 • http://www.newport.nl • e-mail: sales@newport.nl

Newport Electronics spol s.r.o.

Rudé armády 1868, 733 01 Karviná 8 • Czech Republic

TEL: +420 69 6311899 • FAX: +420 69 6311114

Toll Free: 0800-1-66342 • http://www.newport.cz • e-mail: sales@newport.cz

Newport Electronics GmbH

Daimlerstrasse 26 • D-75392 Deckenpfronn • Germany

TEL: 49 7056 9398-0 • FAX: 49 7056 9398-29

Toll Free: 0800 / 6397678 • http://www.newport.de • e-mail: sales@newport.de

Newport Electronique S.A.R.L.

11, rue Jacques Cartier • 78280 Guyancourt • France

TEL: +33 1 61 37 29 00 • FAX: +33 1 30 57 54 27

Toll Free: 0800 466 342 • http://www.newport.fr • e-mail: sales@newport.fr

Mexico and Latin America

TEL: 001-800-826-6342 • FAX: 001 (203) 359-7807

En Español: 001 (203) 359-7803

M2548/N/0802

Warranty/Disclaimer

NEWPORT Electronics, Inc. warrants this unit to be free of defects in materials and workmanship
for  a  period  of 

one (1)  year

from  the  date  of  purchase.  In  addition  to  NEWPORT’s  standard

waranty  period,  NEWPORT Electronics  will  extend  the  warranty  period  for 

four (4)  additional

years

if the warranty card enclosed with each instrument is returned to NEWPORT.

If the unit malfunctions, it must be returned to the factory for evaluation.  NEWPORT’s Customer
Service  Department  will  issue  an Authorized  Return  (AR)  number  immediately  upon  phone  or
written  request.  Upon  examination  by  NEWPORT,  if  the  unit  is  found  to  be  defective,  it  will  be
repaired or replaced at no charge. NEWPORT’s WARRANTY does not apply to defects resulting
from any action of the purchaser, including but not limited to mishandling, improper interfacing,
operation  outside  of  design  limits,  improper  repair,  or  unauthorized  modification.  This
WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence
of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration;
improper  specification;  misapplication;  misuse  or  other  operating  conditions  outside  of
NEWPORT’s  control.  Components  which  wear  are  not  warranted,  including  but  not  limited  to
contact points, fuses, and triacs.

NEWPORT  is  pleased  to  offer  suggestions  on  the  use  of  its  various  products.  However,
NEWPORT  neither  assumes  responsibility  for  any  omissions  or  errors  nor  assumes
liability  for  any  damages  that  result  from  the  use  of  its  products  in  accordance  with
information provided by NEWPORT, either verbal or written. NEWPORT warrants only that
the parts manufactured by it will be as specified and free of defects. 

NEWPORT  MAKES  NO  OTHER  WARRANTIES  OR  REPRESENTATIONS  OF  ANY KIND
WHATSOEVER,  EXPRESS  OR  IMPLIED,  EXCEPT  THAT  OF  TITLE,  AND  ALL IMPLIED
WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR PURPOSE ARE HEREBY DISCLAIMED. 

LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and
the  total  liability  of  NEWPORT  with  respect  to  this  order,  whether  based  on  contract,
warranty,  negligence,  indemnification,  strict  liability  or  otherwise,  shall  not  exceed  the
purchase  price  of  the  component  upon  which  liability  is  based.  In  no  event  shall
NEWPORT be liable for consequential, incidental or special damages.

CONDITIONS:  Equipment sold by NEWPORT is not intended to be used, nor shall it be used:
(1) as a "Basic Component" under 10 CFR 21 (NRC), used in or with any nuclear installation or
activity; or (2) in medical applications or used on humans.  Should any Product(s) be used in or
with any nuclear installation or activity, medical application, or used on humans, or misused in any
way, NEWPORT assumes no responsibility as set forth in our basic WARRANTY/DISCLAIMER
language, and, additionally purchaser will indemnify NEWPORT and hold NEWPORT harmless
from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.

Direct  all  warranty  and  repair  requests/inquiries  to  the  NEWPORT Customer  Service  Department.
BEFORE  RETURNING ANY PRODUCT(S)  TO  NEWPORT,  PURCHASER  MUST OBTAIN AN
AUTHORIZED  RETURN  (AR)  NUMBER  FROM  NEWPORT’S  CUSTOMER  SERVICE  DEPARTMENT
(IN ORDER TO AVOID PROCESSING DELAYS).  The assigned AR number should then be marked on
the outside of the return package and on any correspondence.

The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent
breakage in transit.

FOR WARRANTY RETURNS, please have the
following information available BEFORE 
contacting NEWPORT:

1. P.O. number under which the product was

PURCHASED,

2. Model and serial number of the product under

warranty, and

3. Repair instructions and/or specific problems

relative to the product.

FOR NON-WARRANTY REPAIRS, consult
NEWPORT for current repair charges.  Have the
following information available BEFORE contacting
NEWPORT:

1. P.O. number to cover the COST of the repair,
2. Model and serial number of product, and
3. Repair instructions and/or specific problems

relative to the product.

NEWPORT’s policy is to make running changes, not model changes, whenever an improvement is
possible.  This affords our customers the latest in technology and engineering.

NEWPORT is a registered trademark of NEWPORT Electronics, Inc.

© Copyright 2002 NEWPORT Electronics, Inc.  All rights reserved.  
This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic
medium or machine-readable form, in whole or in part, without prior written consent of NEWPORT
Electronics, Inc.

PATENT NOTICE: This product is covered by one or more of the following patents: U.S. Pat. No.
Des.  336,895;  5,274,577;  6,243,021  /  CANADA 2052599;  2052600  /  ITALY 1249456;  1250938  /
FRANCE  BREVET No.  91  12756  /  SPAIN  2039150;  2048066  /  UK  PATENT No.  GB2  249  837;
GB2 248 954 / GERMANY DE 41 34398 C2. OTHER INTERNATIONAL PATENTS PENDING.

Return Requests/Inquiries

OPERATION MANUAL

Reviews: