3.87
EDH0162En1040 – 06/99
MM4005
NT — Start definition of a new trajectory
Usage
IMM
PGM
MIP
Syntax
NT
Parameters
None.
Description
This command tells to the controller to reset the trajectory buffer and to get
ready to load a new trajectory for execution. NT sets the initial position (X,
Y) and first tangent angle to 0.0.
Returns
None.
Errors
D
—
Unauthorized execution.
S
—
Communication time-out.
Rel. Commands
EL
—
Erase the last element of trajectory.
LT
—
Extended list of the trajectory.
XE
—
Tell the last element.
Example
NT
|
Reset current trajectory.
OA — Set home search acceleration
Usage
IMM
PGM
MIP
Syntax
xxOAnn
Parameters
Description
xx
[int]
— Axis number.
nn
[int]
— Acceleration value.
Range
xx
—
1
to
4.
nn
—
1 E
-6
to
the programmed value in SETUP mode.
Units
xx
— None.
nn
— Preset units in SETUP mode/sec
2
.
Defaults
xx
Missing: Error B.
Out of range: Error B.
Floating point: Error A.
nn
Missing: Error C.
Out of range: Error C.
Description
This command sets the acceleration and deceleration portion of the veloci-
ty profile generator for home search. All subsequent home search accelera-
tions and decelerations will be executed with the new value.
Returns
None.
Errors
A
—
Unknown message code.
B
—
Incorrect axis number.
C
—
Parameter out of limits.
Rel. Commands
OH
—
Set home search high velocity.
OL
—
Set home search low velocity.
OR
—
Search for home.
Example
3OA50
|
Set home search acceleration to 50 units/sec
2
for axis #3.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com