6.13
EDH0162En1040 – 06/99
MM4005
Feature Descriptions Tutorial
Error Reporting: TD Command
Before running a program, the MM4005 does an initial verification of the
code, refusing execution if an error is detected. In other instances, a pro-
gram is aborted automatically during execution if an unpredictable error
occurs. In both cases, the controller stores the error type and the user can
read it with the TB command.
To help even more in troubleshooting a motion program, the MM4005 con-
troller also stores the line which caused the error. Using the TD command,
the user can list the bad or the offending program line.
Integral Gain Saturation Limit: KS Command
The PID servo filter has been extended to include user control over the
integral gain saturation limit. The xxKSnn command can be used to set the
integral gain saturation limit for each axis. The nn parameter range is
expressed between 0 and 1, and represents the saturation level reduction.
Program Editing: EP Command
The EP (enter program mode) command accepts a nn parameters that
allows the user to insert command lines anywhere inside an existing pro-
gram.
The XL command offers the capability to erase a specific command line.
Using the two commands, a program can be edited with a “dumb” terminal,
without having to download it to an external computer/editor.
Firmware Updates
The firmware updates of MM4005 will no longer erase the user program
section of the non-volatile RAM. Only controller setup parameters will be
changed, motion programs will stay intact, if both buttons
and
are pressed at the moment of power on.