Floor temperature min and max
This setting has two main purposes. In floor mode min and max values
specify active range of dial. In dual mode this setting does not effect the dial
but thermostat keeps floor temperature between limits. Feature can be used
to protect wooden floors (max limit) or to guarantee warm floor in room
with fireplace, e.g. Note: N/A in PWM and in air mode.
Floor temperature offset (calibration)
If user’s temperature measurement has offset to dial setpoint this setting
is used to calibrate.
Note, floor sensor inside floor construction is much
warmer than real temperatures measured in room. Thus default is -3C to
have rotary dial adjustment range in realistic area of 18C...24C.
Air temperature min and max
This setting has two main purposes. In air and dual mode it specifies ac-
tive dial range. In all other modes it can be used as air over temperature
protection.
Air temperature offset (calibration)
If user’s temperature measurement has offset to dial setpoint this setting is
used to calibrate.
PWM min and max
This setting has two main purposes. In PWM mode min and max values
specify active dial range. In all other modes it guarantees maximum pulse