Zigbee DALI TW Converter with power supply

If the actuator is operated without a gateway, connect the actuator to a transmitter via
Touchlink within 5 minutes after switching on the mains voltage.

A more detailed configuration can only be carried out with the NEXENTRO Config App.

 DANGER!

Mortal danger of electric shock.

The following work must - unlike commissioning with App -be carried out under
mains voltage and therefore may only be carried out by an electrician!

Only use insulated tools for the work! Cover up live parts in the working environ-
ment.

Setting the minimum brightness

Press the Prog. button for longer than 4 seconds and release it.
The LED lights up green.

Press and hold the Prog. button for longer than 1 second.
The light switches to the lowest brightness and slowly becomes brighter. The LED flashes
green.

Once the desired brightness is reached, release the button Prog..
The current brightness is adopted as the minimum brightness and the LED lights up
green.

Press the Prog. button for less than 1 second or wait 30 seconds to return to normal oper-
ation.

9

Reset device

Deleting assignment to the Zigbee network and Bluetooth coupling

Switch off the supply voltage to the device four times in quick succession and switch it on
again. The pause between switching operations must be less than two seconds.
The actuator acknowledges the deletion of the network assignment and the Bluetooth
coupling to mobile end devices by flashing the light twice.

Restoring the device to factory settings

The device deletes the assignment to a network and all connections to Zigbee devices. Alternat-
ively, the device can also be reset with the NEXENTRO Config App.

 DANGER!

Mortal danger of electric shock.

The following work must be carried out under mains voltage and therefore may only
be carried out by an electrician!

Only use insulated tools for the work! Cover up live parts in the working environ-
ment.

Precondition: Load is switched off.

Press the Prog. button (6) for longer than 20 seconds.
After approx. 20 seconds, the LED flashes rapidly alternately red and green.

Within 10 seconds, release the button and actuate it briefly once again.
The LED flashes more slowly alternately red and green, the device is reset to the default
settings and is restarted.

6 / 8

82403710

17.11.2021

Summary of Contents for 57007000

Page 1: ...f the electrical system and there is a risk of serious damage to property e g through fire You are at risk of personal liabil ity for personal injury and damage to property Contact an electrical contractor Danger of electric shock Always disconnect before carrying out work on the device or load In so doing take all the circuit breakers into account which support dangerous voltages to the device an...

Page 2: ...ure Adjusting the brightness Long press on the push button Adjust the brightness The dimming direction is changed with each new long actuation Switch light on with minimum brightness Press push button continuously with the load switched off Light switches on at minimum brightness and gets brighter Setting the colour temperature Press the push button in the switched on state twice within 0 4 second...

Page 3: ...rk on the device or load disengage all the corresponding cir cuit breakers secure against being switched on again and check that there is no voltage Figure 2 Connection example 8 DALI TW luminaire DT6 9 DALI luminaire or DALI TW luminaire DT8 10 Push button normally open contact Figure 3 Clampable conductor cross section DALI cable type cross section and routing according to the specifications for...

Page 4: ...lour temperature Connecting the actuator with Zigbee transmitters actuators or gateways Indication of the switching status On Off brightness value and colour temperature Displaying device information Device type software version hardware version Performing a software update Resetting to default setting Operating the actuator for test purposes Registering new devices in the NEXENTRO Config app NEXE...

Page 5: ... network was created Switch to the NEXENTRO actuator to be added to the Zigbee network Select the Join Network function The actuator joins the Zigbee network All available devices that can be controlled via the sensor function of the actuator are shown Select the devices Joining a Zigbee network with a NEXENTRO actuator via Touchlink Requirement The distance between the Zigbee transmitter and the ...

Page 6: ...ds to return to normal oper ation 9 Reset device Deleting assignment to the Zigbee network and Bluetooth coupling Switch off the supply voltage to the device four times in quick succession and switch it on again The pause between switching operations must be less than two seconds The actuator acknowledges the deletion of the network assignment and the Bluetooth coupling to mobile end devices by fl...

Page 7: ...utput DT8 DT8 only 25 Output DT6 2 per output Additionally 12 DT8 devices are possible Zigbee Communication protocol Zigbee 3 0 router Radio frequency 2 400 2 483 GHz Transmission capacity 1 mW Bluetooth Radio frequency 2 402 2 480 GHz Transmission capacity max 2 5 mW Class 2 Transmitting range typ 10 m 11 Declaration of conformity Insta GmbH hereby declares that the radio system type art no 57007...

Page 8: ...verter with power supply Insta GmbH Service Center Hohe Steinert 10 58509 Lüdenscheid Germany Insta GmbH Postfach 1830 58468 Lüdenscheid Germany Telefon 49 0 2351 936 0 www insta de info insta de 8 8 82403710 17 11 2021 ...

Reviews: