www.nextups.eu
50
E
n
g
lish
7. Specifications
This chapter provides the following specifications:
Model list
General Specification
Electrical Performance
Environmental and Safety
7.1 Electrical specification
Model
LOGIX II 6000
LOGIX II 10000
Output
Power Capacity
6KVA/5.4KW
10KVA/9KW
Voltage Range
208VAC/220VAC/
230VAC/ 240VAC
208VAC/220VAC/
230VAC/ 240VAC
Frequency
50/60Hz
50/60Hz
Voltage Distortion
<5%@Nonlinear load
<2%@Linear load
<5%@Nonlinear load
<2%@Linear load
Over Load
Line Mode:
2mins 102% ~ 130%
30s
130% ~ 150%
100ms >150%
Battery Mode:
10s
102% ~ 130%
100ms >130%
Efficiency
Line mode
>92%
>93%
ECO mode
>96%
>97%
Battery mode
>89%
>90%
Input
Input wire
1 Ph (L1,L2/N)+ PE
Input Type
Support dual input
Phase
single
Voltage Range
176-276Vac
Frequency Range
(45~55)/(54~66)Hz