TRACE
MATE
2.3
Chapter 2
Installation
Mounting the Controller
Mount the control panel with Unistrut brackets using 3/
8” bolts. The Unistrut (or equivalent) mounting allows
air circulation to cool the heat-sink. This is important to
ensure proper operation of the Tracemate. Mounting
dimensions are shown in Figure 2.5.
Wire Sizing
Conduit and Cabling
TraceMate comes with one 3/4” and 1/2” conduit
knockouts located on the bottom of the enclosure.
Conduit hubs should be NEMA-4X rated, such as T&B
H050-0.5 and H075-0.75 or Myers equivalent, to
maintain a watertight seal. Unused knockouts should be
sealed using NEMA-4X rated seals.
Power Wiring
The power input terminals supply power to both the heat
trace and controller. Size power input wires appropriately
to the breaker size and maximum ambient operating
temperatures. Maximum breaker size is 30A. Connect
power wires to input terminals 1 and 2. See Figure 2.2.
The RTD probe is delicate and should not
be bent or used as a tool to puncture
insulation.
Wiring methods should comply with Canadian
Electrical or National Electrical Code and
local codes. Power and signal wires should not
be run in the same conduit system. Wiring
should be rated at least 90 °C.
Wire Size (AWG)
Current Load (A)
Max. Ambient
Temperature (°C)
6
30
50
8
30
40
10
24
50
12
16
50
The supply voltage must be 120VAC for TM-
1SIH1-E5-RTD ( Single-pole ) or 208-240VAC
for TM-1DIH2-E5-RTD ( Dual-pole ) and
rated voltage range of the heat trace cable.
Wiring methods must conform to Class 1,
Division II or Class 1, Zone II requirements.
Heater Wiring
Connect heating cable wiring to terminals 3 and 4. See
Figure 2.2. If the heating cable has a braid, it should be
terminated to the ground stud using a ring terminal
suitable for #10 stud.
Figure 2.3 Ground Connection
Ground Connection
Connect the controller grounding stud directly to a ground
bus using the shortest, practical path. Use a tinned copper,
braided bonding cable such as Belden 8660. As a guide-
line, the ground cables should be minimum 96 strands,
number 34 AWG each.
To install the ground connection, remove the outside nut,
washer and #8 ring lug provided on the ground stud.
Crimp the ground cable onto the ring lug and re-assemble
onto the ground stud using the washer and nut.
Figure 2.4 RTD Mounting
RTD Sensor Wiring
RTD sensors should be 3-wire, 100 ohm, platinum to
DIN standard 43760. Mount the RTD element on the
pipe, away from the heat trace and 30° to 45° from the
bottom of the pipe. The total circuit resistance per
conductor from the RTD to the control panel must be
less than 10 ohm. Exceeding this resistance will result in
a non-linear temperature measurement. Belden cable
8770 or equivalent allows RTDs to be placed up to 1,000
feet from the control panel. Complete all RTD wiring
according to Figure 2.2 Typical Wiring Diagram.