NPS2400
User’s Manual
Rev. 3.0
– 17.02.2015
Page 14/38
4.3.6
Output current remote measurement
Figure 12
0…10V output for SMPS output current remote measure connection
Figure 13
4…20mA output for SMPS output current remote measure connection
The NPS2400 provides 2 different outputs for the remote measurement of the current delivered by the device.
The 2 outputs follow 2 major industry standards levels:
0…10V voltage output:
0V corresponds to 0A output, 10V corresponds to the rated output current of the SMPS
4…20mA current output:
4mA corresponds to 0A output, 20mA corresponds to the rated output current of the SMPS
Note
: The 2 outputs are floating with respect to the SMPS output (opto-isolated), but their ground is common to GND AUX.
Take care of ground loops when using the remote current measurement in conjunction with the 12 V auxiliary output.
Respect the connection polarity!