NPS2400
User’s Manual
Rev. 3.0
– 17.02.2015
Page 23/38
6.3.1
Power ON test screen
Action:
6.3.2
ID screen
Device Name:
Device Serial Number:
6.3.3
Default screen
This is the screen that appears any time if there is no activity on the other menus for >1 minute. It shows the on going alarms (if
present) or the on-line values of the main parameters of the unit.
Error or Alarm type:
Offending value:
Line 1 shows the error or alarm type, while line 2 shows the offending value causing it.
When an alarm is present the
ALARM
LED is ON and the buzzer is active (if enabled).
If no error or alarms are present and the mode is set to OVERBOOST or CURRENT-LIMIT the most significant measures are
shown.
Uin, Pout:
Uout, Iout:
If no error or alarms are present and the mode is set to BATTERY-CHARGER the charger status and other useful measures are
shown:
Charger status, Temperature:
Uout, Iout:
The available charger statuses are:
BC_CC
: Constant Current charge in process
BC_CV
: Constant Voltage charge in progress
BC_FLOAT
: Float Charge in progress
BC_OT
: Battery environment over-temperature condition ( >50°C)
– only if provided with optional Temp. sensor
BC_ERROR
: Battery is faulty or not connected
BC_REVIVE
: Charger is trying to revive the battery
BC_CHECK
: Battery is checked by the charger
NPS2400X
xxxxxxxxxxxxxxxx
Ui=xxxV Po=x.xkW
Uo=xx.xV I=xxxA
OL Alarm
Iout=103A
BC_FLOAT xx.xC
Uo=xx.xV I=xxxA
Self test
in progress
…