NPS2400
User’s Manual
Rev. 3.0
– 17.02.2015
Page 25/38
6.4.1
Power Limit
Setting:
Value:
In case of operation in high temperature environment is possible to reduce the maximum power of the device. Possible choices
are 1500W/2000W/2400W.
Default
:
2400W
6.4.2
Vin min alarm
Setting:
Value:
Use the UP/DOWN keys to select the
minimum input voltage
alarm threshold. Possible range is:
340 V < Vin min alarm < Vin max Alarm.
Default
:
340V
6.4.3
Vin max alarm
Setting:
Value:
Use the UP/DOWN keys to select the
maximum input voltage
alarm threshold. Possible range is:
Vin min alarm < Vin max alarm < 520V
Default
:
520V
6.4.4
Vout
Setting:
Value:
Use the UP/DOWN keys to set the
desired output voltage
within the possible values for each model
. The range is model
dependent and shown in Table 1.The actual output current is displayed in square brackets
Default:
24.00V / 48.00V / 72.00V / 170.0V
(model dependent)
6.4.5
Nominal Iout
Setting:
Value [actual output voltage]:
Use the UP/DOWN keys to set the desired
nominal output current
. In case of OVERBOOST mode 150% of this value is
supplied for a maximum of 5 consecutive seconds. When the current exceeds this value an overload condition is triggered. The
actual output voltage is displayed in square brackets.
Default
:
100A / 50A / 33A / 14A
(model dependent)
Power limit:
2400W
Vin min alarm:
340V
Vin min alarm:
520V
Vout:
24.00V [Io=0.0A]
Iout nom:
100A [Vo=24.00V]