6.4.18
Relay active on
“DC OK”
Setting:
Value:
Use the UP/DOWN key to enable/disable
the relay on
“DC OK”,
the relay is excited when
Vout>0.9*Vout_set
. In BATTERY-
CHARGER mode this relay function is disabled.
Default:
ENABLED
6.4.19
Relay active on
“Iout OK”
Setting:
Value:
Use the UP/DOWN keys to enable/disable
the relay on
“Iout OK”,
the relay is excited when
Iout<Iout_alarm.
In BATTERY-
CHARGER mode this relay function is disabled.
Default
:
DISABLED
6.4.20
Relay active on
“Temperature OK”
Setting:
Value:
Use the UP/DOWN key to enable/disable the
relay on “Temperature OK”
, the relay is excited when the internal transformer
temperature is < 110°C (230°F).
In BATTERY-CHARGER mode this relay function is disabled.
Default:
DISABLED
6.4.21
Relay active on
“AC OK”
Setting:
Value:
Use the UP/DOWN key to enable/disable the relay on
“AC input OK” (means the AC voltage is within the user defined window),
the relay is excited when the
Vin_min_alarm<Vin<Vin_max_alarm
. In BATTERY-CHARGER mode this relay function is
disabled.
Default
:
DISABLED
6.4.22
Product name
Setting:
Value:
Use UP/DOWN key to change character and OK key to increment to the next string character.
Default
:
NPS2400
Relay DC OK:
ENABLED
Relay Iout OK:
DISABLED
Relay Temp OK:
DISABLED
Relay AC OK:
DISABLED
Product name:
NPS2400