NPSM20 Series

Instruction Manual

NPSM20 Series V4.0

www.nextys.com

Page 5/5

Dismounting:

1.

Pull down the slide clamp lever

2.

Tilt the unit upward

3.

Unhook the unit from the rail

1 & 2

3

Fig.5

Recommended connecting cable

Recommended Tightening torque

0.8 Nm

7.8 lbf in

Solid: 2.5mm² / 12AWG

Stranded:1.5mm² / 12AWG

L: 5.5-6.5mm / 0.22-0.26 in

Fig.6

Input protection

Fuse 6AT or MCB 6A C curve.

For USA and Canada, use the fuse type closest to the European equivalent type.

Surge protection:

it is strongly recommended to provide external surge arresters (SPD) according to local regulations.

Fig.7

Input connections

AC Line

DC Line

Fig.8

Environment

Operating temperature

Derating

- 40°C…70°C

5…95% r.H. non condensing

UL Certified up to 50°C

Overtemperature protection

- 0.5W/°C over 50°C

Note:

Data may change without prior notice in order to improve the product.

Please refer to the latest version of the "Instruction Manual" for each product by visiting

www.nextys.com

See also the products below that can be used in conjunction with NPSM20 units:

(accessory device)

OR20

20A Active ORing controller

NBP30

Sealed Lead acid Battery pack