e
Electro Industries/GaugeTech
Doc # E134-7-15 V1.01
6-2
6.3: Normal Mode
6.3: Normal Mode
n
Normal Mode is the same for the 0-1mA and the 4-20mA Analog Output Modules except for the
number of processes performed by the modules.
Both devices:
1. Accept new values through communication.
2. Output current loops scaled from previously accepted values.
The 0-1mA module includes one more process in its Normal Mode:
3. Read and averagae the A/D and adjust values for Process 2 above
.
n
The device will operate with the following default parameters:
Address
247 (F7H)
Baud Rate
57600 Baud
Transmit Delay Time
0
n
Normal Operation is prevented by a number of occurrences. See Chapter 5 for details.
6.3.1: Output Value, Channels 1-8
6.3.1: Output Value, Channels 1-8
n
Registers 04097-04112 (0x01000-0x0100).
Each channel has two registers. The reading has a 4-byte signed integer. The range is
+2,147,483,647 / -2,147,483,648. The user defines the unit. These values represent inputs from
outside the device The scale and units for an Output Value register should be consistent with those
as programmed in the Scale Hi Value and Scale Lo Value registers for a given channel.
6.3.2: Scale Hi/Lo Value, Channels 1-8
6.3.2: Scale Hi/Lo Value, Channels 1-8
n
Registers 45073-45104 (0x0B010-0x0B02F).
Each channel has two registers. The reading has a 4-byte signed integer. The range is
+2,147,483,647 / -2,147,483,648. The user defines the unit. These values are used with Scale
Hi/Lo Percentage Values in order to find proper current output for a given channel.
6.3.3: Scale Hi/Lo Percent, Channels 1-8
6.3.3: Scale Hi/Lo Percent, Channels 1-8
n
Registers 45105-45120 (0x0B030-0x0B03F).
Each register contains a 2-byte signed integer. The range is +327.67 % - -327.67 % and the unit if
0.01 %. These values are used with Scale Hi/Lo Value Registers in order to find proper current
output for a given channel.
Summary of Contents for I/O Module
Page 2: ......
Page 6: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 iv ...
Page 10: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 viii ...
Page 30: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 2 16 ...
Page 44: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 4 8 ...
Page 50: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 6 4 ...
Page 52: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 7 2 ...
Page 63: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 8 4 ...
Page 65: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 9 2 ...
Page 72: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 10 4 ...
Page 74: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 11 2 ...
Page 81: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 13 2 ...
Page 87: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 14 4 ...
Page 89: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 15 2 ...