10-3
10.4.3: Relay On/Off Timers
10.4.3: Relay On/Off Timers
n
Registers 04100-04107 (0x01003 - 0x01003)
The value in these registers will start to decrement upon receiving Pulse On/Off Commands. The
unit of value in these registers is 0.01 second. The proper On/Off Timer values should be written
before using Pulse On/Off Commands.
10.4.4: Latch On/Off Commands
10.4.4: Latch On/Off Commands
Upon receiving a Latch On Command, the device will make contact between NO (Normal Open)
and Common for the relay selected.
Upon receiving a Latch Off Command, the device will make contact between NC (Normal Close)
and Common for the relay selected.
10.4.5: Pulse On/Off Commands
10.4.5: Pulse On/Off Commands
These commands will work with the values in Relay On/Off Timer registers.
Upon receiving a Pulse On Command, the device will make contact between NO (Normal Open)
and Common for the time in Relay On Timer and make contact between NC (Normal Close) and
Common for the time in Relay Off Timer. Then, the relay will stay at NC (Normal Close).
The values in Relay On/Off Time Registers will become zeros. For another Pulse Command, the
Timer On/Off values should be given to the device again.
Upon receiving a Pulse Off Command, the device will make contact between NC (Normal Close)
and Common for the time in Relay Off Timer and make contact between NO (Normal Open) and
Common for the time in Relay On Timer. Then the relay will stay at NO (Normal Open).
The values in Relay On/Off Time Registers will become zeros. For another Pulse Command, the
Timer On/Off values should be given to the device again.
For example, in order to have Relay 1 do a 4-second Pulse On, do the following steps:
1. Write 4000 to Register 04101 (0x01004) for Relay On Timer.
2. Write 0 to Register 04098 (0x01001) to select Relay 1.
3. Write 3 to Register 04099 (0x01002) to send Pulse On Command.
Upon receiving this command, the device will make contact between NO (Normal Open) and
Common for 4 seconds and make contact between NC (Normal Close) and Common.
Summary of Contents for I/O Module
Page 2: ......
Page 6: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 iv ...
Page 10: ...e Electro Industries Gauge Tech Doc E134 7 15 V1 01 viii ...
Page 30: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 2 16 ...
Page 44: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 4 8 ...
Page 50: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 6 4 ...
Page 52: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 7 2 ...
Page 63: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 8 4 ...
Page 65: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 9 2 ...
Page 72: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 10 4 ...
Page 74: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 11 2 ...
Page 81: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 13 2 ...
Page 87: ...e Electro Industries GaugeTech Doc E134 7 15 V1 01 14 4 ...
Page 89: ...e Electro Industries Gauge Tech Doc E 134 7 15 V1 01 15 2 ...