4. Advanced Operation
PROGRAMMABLE AC POWER SOURCE
190
3.
Enable/Disable the energization. The power unit on which the energization is enabled/disabled
is represented by
/
respectively. Move the cursor to
/
and press the ENTER key to
switch between
and
.
4.
Select [OK]. The energization is enabled or disabled and the window is closed.
--------
Notes
----------------------------------------------------------------------------------------------------------------
The maximum current, current monitor gain, current measurement full scale, and the power
measurement full scale are set to the values corresponding to the rated output power which is
determined by the number of power units to be energized. However, the applied current
measurement accuracy and the power measurement accuracy are the values under the
condition where all power units are enabled for energization.
If the number of the energized power units is changed, the setting values of the peak current
limiter and the RMS current limiter are restored to the factory default settings corresponding to
the rated power which is determined by the number of the power units to be energized.
If you select [OK] without changing the energization settings in the power unit energization
setting window, the energization settings of all power units are disabled once and enabled
again. The setting values of the peak current limiter and the RMS current limiter are restored
to the factory default settings corresponding to the rated power which is determined by the
number of the power units to be energized.
For a polyphase system, the number of power units on which the energization is enabled must
be same on all phases.
If a failure occurs in a power unit for some reason, you can disable the energization for that
unit to restart using this product with the remaining power units. For details, see
---------------------------------------------------------------------------------------------------------------------------------
Summary of Contents for DP015S
Page 1: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL NF Corporation ...
Page 2: ......
Page 3: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL DA00027113 001 ...
Page 4: ......
Page 18: ......
Page 24: ...1 Outline PROGRAMMABLE AC POWER SOURCE 6 ...
Page 224: ...5 Description of Screen and Menu PROGRAMMABLE AC POWER SOURCE 206 ...
Page 238: ...7 Options PROGRAMMABLE AC POWER SOURCE 220 ...
Page 298: ......
Page 300: ......
Page 302: ......
Page 303: ......