10. Specifications
PROGRAMMABLE AC POWER SOURCE
252
Power (reactive power is optional)
Single-phase model, Polyphase model, Multi-phase model
015S, 030D, 045T
045M (polyphase
output)
030S, 060D, 090T
090M (polyphase
output)
045S
045M
(single-phase
output)
090D
Full scale
1800 W
3600 W
5400 W
Resolution
0.1 W/1 W (1000 W or higher)
DC, 45 Hz to 65 Hz
Enable
(W)
Accuracy
±
(1% of rdg
+ 1.5 W)
±
(1% of rdg
+ 1.5 W)
±
(1% of rdg
+ 2.25 W)
±
(1% of rdg
+ 3 W)
Full scale
2250 VA
4500 VA
6750 VA
Resolution
0.1 VA/1 VA (1000 VA or higher)
45 Hz to 65 Hz
Apparent
(VA)
Accuracy
±
(2% of rdg
+ 3 VA)
±
(2% of rdg
+ 3 VA)
±
(2% of rdg
+ 4.5 VA)
±
(2% of rdg
+ 6 VA)
Full scale
2250 var
4500 var
6750 var
Resolution
0.1 var/1 var (1000 var or higher)
45 Hz to 65 Hz
Reactive
(var)
Accuracy
±
(2% of rdg
+ 3 var)
±
(2% of rdg
+ 3 var)
±
(2% of rdg
+ 4.5 var)
±
(2% of rdg
+ 6 var)
Single-phase model, Single-phase three-wire model, Single-phase output of the
Multi-phase model
060S, 120D
075S
090S, 090M
105S
120S
Full scale
7200 W
9000 W
10800 W
12600 W
14400 W
Resolution
0.1 W/1 W (1000 W or higher)
DC, 45 Hz to 65 Hz
Active
(W)
Accuracy
±
(1% of rdg
+ 3 W)
±
(1% of rdg + 4.5 W)
±
(1% of rdg + 6 W)
Full scale
9000 VA
11250 VA
13500 VA
15750 VA
18000 VA
Resolution
0.1 VA/1 VA (1000 VA or higher)
45 Hz to 65 Hz
Apparent
(VA)
Accuracy
±
(2% of rdg
+ 6 VA)
±
(2% of rdg + 9 VA)
±
(2% of rdg + 12 VA)
Full scale
9000 var
11250 var
13500 var
15750 var
18000 var
Resolution
0.1 var/1 var (1000 var or higher)
45 Hz to 65 Hz
Reactive
(var)
Accuracy
±
(2% of rdg
+ 6 var)
±
(2% of rdg + 9 var)
±
(2% of rdg + 12 var)
Note: All in the case of sine wave, 50 V or higher output voltage, and that the output current is 10% or higher of
the maximum current.
Note: In the polyphase model, polyphase system, and polyphase output of the Multi-phase, these are the
specifications for each phase.
Note: In the polyphase model, polyphase system, and polyphase output of the Multi-phase, the all-phase total
display is available.
Note: The active power is for the load with the power factor 1. In the case of the load with the power factor 0.5 to
lower than 1, the accuracy is twice the value with the power factor 1.
Note: The reactive power is for the load with the power factor 0.5 or lower.
Note: The apparent and reactive powers are not displayed in the DC mode.
Summary of Contents for DP015S
Page 1: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL NF Corporation ...
Page 2: ......
Page 3: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL DA00027113 001 ...
Page 4: ......
Page 18: ......
Page 24: ...1 Outline PROGRAMMABLE AC POWER SOURCE 6 ...
Page 224: ...5 Description of Screen and Menu PROGRAMMABLE AC POWER SOURCE 206 ...
Page 238: ...7 Options PROGRAMMABLE AC POWER SOURCE 220 ...
Page 298: ......
Page 300: ......
Page 302: ......
Page 303: ......