2. Preparation before Use
PROGRAMMABLE AC POWER SOURCE
14
About power input terminal
Table 2-4 Power Input Terminal
DP015, DP030,
DP045, DP060
DP075, DP090,
DP105, DP120
Screw M6 M8
About power input cable
The power input cable supplied with this product varies in diameter depending on the rated output as
shown in Table 2-5. A crimp-type terminal is attached to each cable on the end which is to be
connected to the input terminal of this product.
On the supplied power input cable, the end which is to be connected to the distribution board
has no terminal attached. Use a crimp-type terminal appropriate for the terminal screw
diameter of the distribution board to connect the cable firmly.
The supplied power input cable is dedicated only to this product. Do not use it with any other
product.
When you use a power input cable other than the one supplied with the product, select a cable
which has an appropriate diameter in consideration of the safety standards and consumption
current. Use a protective grounding conductor of which diameter is the same or greater than
the power input cable.
Table 2-5 Maximum Input Power/Current and Power Input Cable
Maximum
Input Current
Supplied power input cable
Rated
output
Maximum
Input
Power
Power
Input
90 V
Power
Input
170 V
For both 100 V and 200 V series
(Power Input 90 V or More)
Only for 200 V Series
(Power Input 170 V or More)
1.5 kVA
2.25 kVA
25 A
13 A
AWG10
(5.5 mm
2
approx.)
AWG14
(2.1 mm
2
approx.)
3 kVA
4.50 kVA
50 A
26 A
AWG6
(14 mm
2
approx.)
AWG10
(5.5 mm
2
approx.)
4.5 kVA
6.75 kVA
40 A
6 kVA
9.00 kVA
53 A
AWG6
(14 mm
2
approx.)
7.5 kVA 11.25 kVA
66 A
9 kVA
13.50 kVA
79 A
AWG4
(22 mm
2
approx.)
10.5 kVA 15.75 kVA
93 A
12 kVA
18.00 kVA
75 A
106 A
AWG2
(38 mm
2
approx.)
Note: The model of which rated output is 6 kVA or less contains either a power cable for both 100 V and 200 V
series input or a power cable only for 200 V series input, depending on the destination of shipment. The
dedicated cable only for 200 V series input must be used with power supply voltage of 170 to 230 V.
Power source connection procedure
Check the current capacity of the single-phase distribution board before wiring. The wiring must be
performed by a professional engineer.
Before connecting this product to the power source, be sure to cut the power to the distribution
board. Otherwise, an electric shock might occur.
WARNING
Summary of Contents for DP015S
Page 1: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL NF Corporation ...
Page 2: ......
Page 3: ...PROGRAMMABLE AC POWER SOURCE DP Series INSTRUCTION MANUAL DA00027113 001 ...
Page 4: ......
Page 18: ......
Page 24: ...1 Outline PROGRAMMABLE AC POWER SOURCE 6 ...
Page 224: ...5 Description of Screen and Menu PROGRAMMABLE AC POWER SOURCE 206 ...
Page 238: ...7 Options PROGRAMMABLE AC POWER SOURCE 220 ...
Page 298: ......
Page 300: ......
Page 302: ......
Page 303: ......