Function Analog select
Direction
PI control
Select A
Select B
Select C
Terminal
Function
DIN2 DIN3 DIN4 DIN5 DIN6 DIN7
Analog 1 Forward
0
0
0
0
0
0
Analog 1 Reverse
0
1
0
0
0
0
Fix-1
F
0 0 0 1 0 0
Fix-1
R
0 1 0 1 0 0
Fix-2
F
0 0 0 0 1 0
Fix-2
R
0 1 0 0 1 0
Fix-3
F
0 0 0 1 1 0
Fix-3
R
0 1 0 1 1 0
Fix-4
F
0 0 0 0 0 1
Fix-4
R
0 1 0 0 0 1
Fix-5
F
0 0 0 1 0 1
Fix-5
R
0 1 0 1 0 1
Fix-6
F
0 0 0 0 1 1
Fix-6
R
0 1 0 0 1 1
Fix-7
F
0 0 0 1 1 1
Fix-7
R
0 1 0 1 1 1
Analog 2 Forward
1
0
0
x
x
x
Analog 2 Reverse
1
1
0
x
x
x
PI control F
x
0
1
x
x
x
PI control R
x
1
1
x
x
x
Table 7. Digital input control to select setpoint source. (0 = inactive, open, 1 = active, closed)
Parameter
Ain Type
Analogue value
Input (terminal)
0-20 mA
Current 0-20mA
20 and 21 (J701 at “I” position)
4-20 mA
Current 4-20mA
20 and 21 (J701 at “I” position)
+/-20 mA
C/- 20mA
20 and 21 (J701 at “I” position)
0-10 V
Voltage 0-10V
20 (J701 at “U” position)
2-10 V
Voltage 2-10V
20 (J701 at “U” position)
+/-10 V
V/- 10V
20 (J701 at “U” position)
Pot
Potentiometer
11, 20 and 27 (J701 at “U” position)
Table 8. Settings for analogue inputs AIN1 and AIN2.
5.4.3 Bus Mode (Serial channel / Field bus)
There are two built in communication protocols available: Modbus RTU/ASCII and NFO Classic (legacy NFO
protocol). Both communicate using either USB or RS485. For other fieldbus communication protocols, the inverter
also accepts an Anybus CompactCom module as an option. Please contact NFO Drives AB for more information.
For controlling the inverter or altering its parameters via Modbus or NFO Classic protocol, the Windows program
“NFO Sinus Manager” is available and can be downloaded from www.nfodrives.se