Protection Settings
Long Time Delay (LTD) protection
32
TemBreak
PRO
P_SE-UM-001-EN
– V1.2.0
Adjusting t
r
(Time Delay)
The t
r
time delay defines the trip time of the long-time delay protection for a current of 6 x I
r
.
Adjustments to t
r
parameter can be made using:
-
P_SE OCR embedded display
-
TPED
-
TPCM
t
r
Adjustment Range (seconds)
0.5
1.5
2.5
5
7.5
9
10
12
14
16
5.
0
s
tr
Notice
: For the following MCCBs the setting of I
r
and t
r
can limit the setting of I
sd
for STD protection.
P160_SE I
n
= 160A, P250_SE I
n
= 250A
If: I
r
> 0.9 x I
n
and t
r
= 16s
I
sd
is limited to 9 x I
r
.
Notice
: The trip time tolerance for LTD protection is -20% + 20ms to 0% + 30ms.
Example:
For t
r
= 5 s and I = 6 x I
r
, the trip time for long time delay protection will be between 4.02 s and 5.03 s.
Summary of Contents for Terasaki TemBreak PRO P SE Series
Page 106: ...106 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex A Dimensions P160 Dimensions...
Page 107: ...Annex A Dimensions 107 TemBreak PRO P_SE UM 001 EN V1 2 0 P250 Dimensions...
Page 108: ...Annex A Dimensions 108 TemBreak PRO P_SE UM 001 EN V1 2 0 P400 Dimensions...
Page 109: ...Annex A Dimensions 109 TemBreak PRO P_SE UM 001 EN V1 2 0 P630 Dimensions...
Page 111: ...111 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex C I2t Let Through Curves P160_SE...
Page 112: ...Annex C I2t Let Through Curves 112 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 113: ...Annex C I2t Let Through Curves 113 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 114: ...Annex C I2t Let Through Curves 114 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 115: ...115 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex D Peak Let Through Curves P160_SE...
Page 116: ...116 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 117: ...117 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 118: ...118 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 121: ...121 TemBreak PRO P_SE UM 001 EN V1 2 0 This page is intentionally left blank...