Measurements and settings
65
TemBreak
PRO
P_SE-UM-001-EN
– V1.2.0
Energy Measurements
The P_SE OCR provides various energy readings by integrating the instantaneous power over a network period and storing the totalised energy in several
counters and incremented once every second.
Active and reactive energy counters provide separate and combined values for produced and consumed energy (i.e. energy flowing through the MCCB in
either direction). Absolute counters are unsigned and combine the total energy in either direction regardless of power sign, whereas net counters are signed
and will subtract produced energy from consumed.
The partial energy counters can be reset using one or a combination of the below methods:
-
P_SE OCR embedded display
-
TPED
-
TPCM
Separate non-resetable counters are made available for produced and consumed active energy only. These are separate to the partial energy counters as
they cannot be reset and are permanently retained in OCR memory.
Partial energy counter
Symbol
User reset
Active energy consumed
E
a In
✓
Active energy produced
E
a Out
✓
Reactive energy consumed
E
r In
✓
Active energy produced
E
r Out
✓
Absolute active energy (In + Out)
E
a Abs
✓
Absolute reactive energy (In + Out)
E
r Abs
✓
Signed total active energy (In
–
Out)
E
a
✓
Signed reactive energy (In
–
Out)
E
r
✓
Total apparent energy
E
s
✓
Total energy counter
Symbol
User reset
Active energy consumed
–
non resetable
Ea In NR
─
Active energy produced
–
non resetable
Ea Out NR
─
Notice
: Accuracy and correct polarity of all energy related measurements are dependent on several calculation,
power flow and sign convention settings. Refer to the respective sections for details on these settings:
Power flow direction and quadrant
Summary of Contents for Terasaki TemBreak PRO P SE Series
Page 106: ...106 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex A Dimensions P160 Dimensions...
Page 107: ...Annex A Dimensions 107 TemBreak PRO P_SE UM 001 EN V1 2 0 P250 Dimensions...
Page 108: ...Annex A Dimensions 108 TemBreak PRO P_SE UM 001 EN V1 2 0 P400 Dimensions...
Page 109: ...Annex A Dimensions 109 TemBreak PRO P_SE UM 001 EN V1 2 0 P630 Dimensions...
Page 111: ...111 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex C I2t Let Through Curves P160_SE...
Page 112: ...Annex C I2t Let Through Curves 112 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 113: ...Annex C I2t Let Through Curves 113 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 114: ...Annex C I2t Let Through Curves 114 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 115: ...115 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex D Peak Let Through Curves P160_SE...
Page 116: ...116 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 117: ...117 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 118: ...118 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 121: ...121 TemBreak PRO P_SE UM 001 EN V1 2 0 This page is intentionally left blank...