Alarms
72
TemBreak
PRO
P_SE-UM-001-EN
– V1.2.0
Custom Alarms
Custom alarms make it possible to produce alarms based specific events and measurements made by the P_SE OCR. They are only available to be
configured and displayed using the TPED and/or TPCM in conjunction with the P_SE MCCB.
Up to 12 custom alarms may be individually configured for a single P_SE OCR, with each used to monitor a single event of measurement.
Custom alarms may also be assigned to the OAC (Optional Alarm Contact) to provide a physical output when the respective custom alarm has been
activated. Refer to
section for more information.
A custom alarm is defined through the following parameters:
-
Measurement monitored
-
Activation threshold
-
Deactivation threshold
-
Activation time delay
-
Deactivation time delay
-
Priority level
Custom alarm parameters
Configuration of custom alarm types, pick-up and drop-out thresholds and time delays can be made using one or a combination of the below methods:
-
TPED
-
TPCM
Refer to the respective device’s User Manual for detailed instructions on how to configure the
custom alarms.
Custom alarms may be configured to activate under specific conditions, which, depending on the event or measurement type may include one or more of
the following parameters:
-
Pick-up threshold
-
Pick-up time delay
-
Drop-out threshold
-
Drop-out time delay
-
Equivalent value
The pick-up threshold in conjunction with its time delay determine the value in which the custom alarm is activated, whereas the drop-out threshold is the
value which de-activates the alarm. One may be set to a value higher or lower than the other, which determines whether the alarm activation is positive or
negative with respect to the change in the measurement value.
Notice
: The use of the OAC physical contact requires the connection of the OAC/PTA cable to the OAC port
located under the front cover of the P_SE MCCB. Refer to the
section for details on the
OAC/PTA cable.
Only one Alarm can be configured to use the OAC at any one time
Summary of Contents for Terasaki TemBreak PRO P SE Series
Page 106: ...106 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex A Dimensions P160 Dimensions...
Page 107: ...Annex A Dimensions 107 TemBreak PRO P_SE UM 001 EN V1 2 0 P250 Dimensions...
Page 108: ...Annex A Dimensions 108 TemBreak PRO P_SE UM 001 EN V1 2 0 P400 Dimensions...
Page 109: ...Annex A Dimensions 109 TemBreak PRO P_SE UM 001 EN V1 2 0 P630 Dimensions...
Page 111: ...111 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex C I2t Let Through Curves P160_SE...
Page 112: ...Annex C I2t Let Through Curves 112 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 113: ...Annex C I2t Let Through Curves 113 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 114: ...Annex C I2t Let Through Curves 114 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 115: ...115 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex D Peak Let Through Curves P160_SE...
Page 116: ...116 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 117: ...117 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 118: ...118 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 121: ...121 TemBreak PRO P_SE UM 001 EN V1 2 0 This page is intentionally left blank...